DCA-400SPK — GENERATOR SHUTDOWN PROCEDURE
Engine Shutdown
To shutdown the generator use the following procedure:
1.Place both the MAIN, GFCI and LOAD circuit breakers to the "OFF position".
2.Let the engine cool by running it for
3.Place the Off/Manual/Auto Switch (Figure 51) in the "OFF/ RESET" position
Emergency Stop
1.To stop the engine in the event of an emergency, PUSH the emergency stop button ( Figure 53) inward.This button is located on the generator's engine operating panel, see page 30, Figure 11.
Figure 53. Emergency Stop Button
Figure 51. Off/Manual Auto Switch (OFF) | CAUTION: |
4.Verify that the "Engine Running" status LED (Figure 52) on the Microprocessor Engine Control Module (MPEC) display is "OFF" (not lit).
NEVER stop the engine suddenly except in an emergency. DO NOT use the emergency stop switch a as method of shutting down the engine. This switch is ONLY to be used in the event of an emergency.
Figure 52. MPEC Engine Running
Status LED (OFF)
5.Remove the load from the UVWO terminal strip (Figure 18 on page 48).
PAGE 52 —