Output Terminal Panel Available Voltages

DCA-500SSK — OUTPUTTERMINAL

CAUTION:

A wide range of voltages are available to supply load to many different applications. Voltages may be selected by using the voltage change-over board and how to hookup the hard wire connection to the voltages listed, fine adjustment with the Voltage Regulator on the control panel is necessary. See the table below (Table 8) for a list of available voltages the generator is able to supply.

NEVER attempt to change the Voltage Change-Over Board with the engine is running.

 

 

TABLE 8. VOLTAGES AVAILABLE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MODEL

DCA500SSK

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3 PHASE VOLTAGE

208 VOLT

 

220 VOLT

 

240 VOLT

 

416 VOLT

 

440 VOLT

480 VOLT

(RECONNECTABLE)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SINGLE PHASE

120 VOLT

 

127 VOLT

 

139 VOLT

 

240 VOLT

 

254 VOLT

277 VOLT

(ADJUSTABLE)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Over Current Relay

 

 

 

 

 

Maximum Amps

 

 

 

An over current relay is connected to the circuit breaker.

 

 

 

The following table below shows the maximum amps the

During an over current situation, both the circuit breaker and

the over current relay may trip. If the circuit breaker can not

generator can provide Do not exceed the maximum amps

be reset, the reset button on the over current relay must be

listed below.

 

 

 

 

pressed. The over current relay is located on the control

 

 

 

 

 

 

box.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Table 9.

Maximum Amps

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Model:

DCA500SSK

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Rated

Maximum Amps

 

 

 

 

 

 

 

Voltage

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Single Phase

1111.1 amps (4 wire)

 

 

 

 

 

 

 

120 Volt

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Single Phase

555.6 amps (4 wire)

 

 

 

 

 

 

 

240 Volt

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Three Phase

1202.8 amps

 

 

 

 

 

 

 

240 Volt

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Three Phase

601.4 amps

 

 

 

 

 

 

 

480 Volt

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PAGE 38 — DCA-500SSK — PARTS AND OPERATION MANUAL (STD) — REV. #1 (04/14/01)

Page 38
Image 38
Multiquip DCA-500SSK Output Terminal Panel Available Voltages, Over Current Relay Maximum Amps, Model, Rated Maximum Amps