Multiquip DCA-500SSK - OUTPUTTERMINAL, Volt Set position, Single Phase, 480 Volt

Models: DCA-500SSK

1 114
Download 114 pages 57.54 Kb
Page 41
Image 41
DCA-500SSK — OUTPUTTERMINAL

DCA-500SSK — OUTPUTTERMINAL

480 Volt Set position

The voltage change-over board 480V set position uses all 6 plates in 3 different connection places. There are 2 plates at every position (Every plate is used). See figure 23 below.

Single Phase, 480 Volt

The following connection, with the voltage change-over board set into the 480V set position (See Figure 23), can offer SINGLE PHASE power at 480V. After hooking up the hard wires to the lugs as shown in figure 25 below, 480V will be the voltage output.

FIGURE 23. Voltage Change-over Board 480V set position.

3 Phase, 480 Volt

The following connection, with the voltage change-over board set into the 480V set position (See Figure 23), can offer THREE PHASE power at 480V. After hooking up the hard wires to the lugs as shown in figure 24 below, 480V will be the voltage output.

FIGURE 25. Hard Wire Hookup for Single Phase 480V

Single Phase, 277 Volt

The following connection, with the voltage change-over board set into the 480V set position (See Figure 23), can offer SINGLE PHASE power at 277V. After hooking up the hard wires to the lugs as shown in figure 26 below, 277V will be the voltage output.

FIGURE 24. Hard Wire Hookup for Three Phase 480V

FIGURE 26. Hard Wire Hookup for Single Phase 277V

DCA-500SSK — PARTS AND OPERATION MANUAL (STD)— REV. #1 (04/14/01) — PAGE 41

Page 41
Image 41
Multiquip DCA-500SSK - OUTPUTTERMINAL, Volt Set position, Single Phase, 480 Volt, Single Phase, 277 Volt