Multiquip operation manual DCA-56SPX- GENERATOR START-UPPROCEDURE AUTO MODE, Starting Auto Mode

Models: DCA-56SPX

1 86
Download 86 pages 44.14 Kb
Page 37
Image 37
DCA-56SPX — GENERATOR START-UP PROCEDURE (AUTO MODE)

DCA-56SPX — GENERATOR START-UP PROCEDURE (AUTO MODE)

Starting (Auto Mode)

DANGER - ELECTRICAL SYSTEM HAZARDS

Before connecting this generator to any building’s electrical system, a licensed electrician must install an isolation (transfer) switch. Serious damage to the building’s electrical system may occur without this transfer switch.

When starting generator in AUTO mode use the "Manual Start-up" procedure except where noted (see below).

1.Perform steps 1 through 5 in the Before Starting section.

2.Place the MPEC Control Switch (Figure 41) in the AUTO position

CAUTION - BACKUP GENERATOR USE

When connecting the generator to a isolation (transfer) switch, ALWAYS have power applied to the generator's internal battery charger. This will ensure that the engine will not fail due to a dead battery.

Figure 41. MPEC Control Switch (AUTO)

3.Continue operating the generator as outlined in the Manual Start-up Procedure (start at step 5).

When the generator is set in the AUTO mode, the generator will

NOTE automically start in the event of comercial power falling below a prescribed level by means of a contact closure that is generated automatically by a transfer switch.

WARNING - AUTO MODE MAINTENANCE

When running the generator in the AUTO mode, remember the generator can start up at any time without warning. NEVER attempt to perform any maintenance when the generator is in the auto mode.

DCA-56SPX— OPERATION AND PARTS MANUAL — REV. #1 (04/14/10) — PAGE 37

Page 37
Image 37
Multiquip DCA-56SPX- GENERATOR START-UPPROCEDURE AUTO MODE, Starting Auto Mode, Danger - Electrical System Hazards