DCA-85USJ — OUTPUT TERMINAL PANEL CONNECTIONS

UVWO Terminal Output Voltages

Various output voltages can be obtained using the Output Terminal Lugs.. The voltages at the terminals are depen- dent on the position of the Voltage Selector Switch and the adjustment of the Voltage Regulator Control Knob.

Remember the voltage selector switch determines the range of the output voltage. The voltage regulator (VR) allows the user to increase or decrease the selected voltage.

3Ø 240/139 Output Terminal Lug Voltages

1.Place the voltage selector switch in the 3Ø 240/139 position as shown in Figure 22.

Figure 22. Voltage Selector Switch 240/139V

Three-Phase Position

2.Connect the load wires to the OutputTerminal Lugs as shown in Figure 22.

3Ø 208V/1Ø120V OutputTerminal Lug Voltages

1.Place the voltage selector switch in the 3Ø 240/139 position as shown in Figure 25.

Use this position for 3Ø-208 or 1Ø120V.

Figure 25. Voltage Selector

Switch 3Ø-208V/1Ø-120V

Three-Phase Position

2.Connect the load wires to the OutputTerminal Lugs as shown in Figure 26.

Figure 26. Output Terminal Lugs

3Ø-208V/120V Connections

3.Turn the voltage regulator knob (Figure 24) clockwise to increase voltage output, turn counterclockwise to decrease voltage output.

Figure 23. Output Terminal Lugs

 

To achieve a 3Ø 208V output

 

the voltage selector switch

240/139VThree Phase Connections

NOTE

must be in the 3Ø-240/139

3. Turn the voltage regulator knob (Figure 23) clockwise to

 

position and the voltage

increase voltage output, turn counterclockwise to

 

regulator must be adjusted to

decrease voltage output.

 

208V.

Figure 24. Voltage Regulator Knob (139V/240V)

PAGE 30 — DCA-85USJ — OPERATION AND PARTS MANUAL — REV. #0 (09/17/04)

Page 30
Image 30
Multiquip DCA-85USJ Output Terminal Panel Connections, Uvwo Terminal Output Voltages, Three-Phase Position