DCA-85USJ — GENERATOR SHUT-DOWN PROCEDURE
WARNING - SHUTTING DOWNTHE GENERATOR
NEVER stop the engine suddenly except in an emergency. DO NOT use the emergency stop switch a as method of shutting down the generator. This switch is ONLY to be used in the event of an emergency.
Shutdown Procedure
To shutdown the generator use the following procedure:
1.Place both the MAIN, GFCI and LOAD circuit breakers as shown in Figure 39 to the OFF position.
3.Let the engine cool by running it for
4.Place the MPEC Control Switch (Figure 55) to the OFF/RESET position.
Figure 55. MPEC Control Switch (Off/Reset)
5.Verify that the all status LED on the MPEC display are OFF (not lit).
6.Remove all loads from the generator.
Emergency Shutdown Procedure
1.To
2.Place the MPEC Control Switch switch (Figure 55) to the OFF/RESET position.
PAGE 40 —