Multiquip GBP5000H manual GDP-5000H - PRE-SETUP, #10 Wire, #14 Wire

Models: GBP5000H

1 76
Download 76 pages 19.3 Kb
Page 12
Image 12
GDP-5000H — PRE-SETUP

GDP-5000HPRE-SETUP

General Inspection Prior to Operation

This generator has been thoroughly inspected prior to shipment from the factory. However, be sure to check for damaged parts or components, or loose nuts and bolts, which could have occurred in transit.

Ground

The nut and ground terminal on the generator should always be used to connect the generator to a suitable ground. The ground path should be of #8 size wire.

Connect the terminal of the ground wire between the lock washer and the nut and tighten the nut fully. Connect their end of the wire to a suitable ground.

Ground the Generator

Ground the generator from its ground connector so that the resistance to ground is 500 ohms or less.

Ground the Tool

Ground the tool (load) in the same manner as the generator.

Circuit Breaker

To protect the generator from an overload, circuit breakers are provided for both 60 and 180 phases on the control box. Make sure to switch the circuit breakers to the "OFF" position prior to starting the engine.

Extension Cable

When electric power is to be provided to various tools or loads at some distance from the generator, extension cords are normally used. Cables should be sized to allow for distance in length and amperage so that the voltage drop between the generator and point of use (load) is held to a minimum. Use the cable selection chart (Tables 2 and 3) as a guide for selecting proper cable size.

Table 2. Cable Selection (60 Hz, single phase operation)

Current

Load In Watts

Maximum Allowable Cable Length

in

At 120

At 240

#10 Wire

#12 Wire

#14 Wire

#16 Wire

Amperes

Volts

Volts

 

 

 

 

 

 

 

 

 

 

 

2.5

300

600

1000 ft.

600 ft.

375 ft.

250 ft.

 

 

 

 

 

 

 

5

600

1200

500 ft.

300 ft.

200 ft.

125 ft.

 

 

 

 

 

 

 

7.5

900

1800

350 ft.

200 ft.

125 ft.

100 ft.

 

 

 

 

 

 

 

10

1200

2400

250 ft.

150 ft.

100 ft.

 

 

 

 

 

 

 

 

15

1800

3600

150 ft.

100 ft.

65 ft.

 

 

 

 

 

 

 

 

20

2400

4800

125 ft.

75 ft.

50 ft.

 

 

 

 

 

 

 

 

CAUTION: Equipment damage can result from low voltage.

Table 3. Cable Selection (180 Hz, 3-phase operation)

Length (ft.)

50

100

150

200

250

300

Load

 

 

 

 

 

 

3 kVA

0.0031 in2

0.0031 in2

0.0031 in2

0.0054 in2

0.0054 in2

0.0085in2

 

 

 

 

 

 

 

2 kVA

0.0031 in2

0.0031 in2

0.0031 in2

0.0031 in2

0.0031 in2

0.0054 in2

 

 

 

 

 

 

 

1 kVA

0.0031 in2

0.0031 in2

0.0031 in2

0.0031 in2

0.0031 in2

0.0031 in2

 

 

 

 

 

 

 

PAGE 12 — GDP-5000H A.C. GENERATOR— OPERATION AND PARTS MANUAL — REV. #2 (07/23/08)

Page 12
Image 12
Multiquip GBP5000H manual GDP-5000H - PRE-SETUP, #10 Wire, #14 Wire