  | TROUBLESHOOTING | 
  | 
  | 
  | 
  | 
  | 
  | 
  | Table 5. Lamp Troubleshooting | |
  | 
  | 
  | 
Symptom | Possible Cause | Solution | 
  | 
  | 
  | 
  | Lamp Burned Out?  | Test the lamp in a fixture which is operating properly.  | 
  | Replace if necessary.  | |
  | 
  | |
  | 
  | Inspect lamp base to see if there is arcing at center  | 
  | Lamp Loose in Socket?  | contact button. Tighten lamp snugly. Check socket for  | 
  | 
  | damage. Replace if defective.  | 
  | 
  | 
  | 
  | Lamp Plugs Not Tight?  | Check plug and receptacle. Tighten if loose.  | 
  | 
  | 
  | 
  | 
  | Interchange ballast plugs in generator enclosure.  | 
  | Defective Ballast? | If lamp starts, replace ballast. Check ballast wiring | 
  | against diagram. Check for swollen capacitor, charred  | |
  | 
  | |
  | 
  | wiring, core and coil or other signs of excessive heat.  | 
  | 
  | Check line voltage at ballast input. Voltage should  | 
  | Low Voltage? | be within 10% of nameplate rating when operating  | 
  | at normal load. Increase supply voltage or remove  | |
  | 
  | |
  | 
  | external load.  | 
Lamp will not start. | 
  | 
  | 
  | Proper HID lamps will perform erratically or fail to  | |
  | 
  | start on an improper ballast. The ballast nameplate  | 
  | Improper Ballast? | data must agree with the line voltage and lamp used.  | 
  | Improper ballast causes lamp failure. Note: Mercury  | |
  | 
  | |
  | 
  | lamps of the same wattage will operate properly on  | 
  | 
  | Metal Halide ballasts. | 
  | 
  | Operating position should agree with the lamp tech.  | 
  | 
  | A   | 
  | Improper Lamp Operating  | and including the horizontal and a BD can be operated  | 
  | Position (Metal Halide only)? | base down vertical to, approaching, but not including  | 
  | 
  | the horizontal. A lamp operated beyond the specified  | 
  | 
  | position may not start. | 
  | 
  | 
  | 
  | 
  | HID lamps (High Pressure Sodium, Metal Halide,  | 
  | Lamp has been Operating: Cool  | Mercury Vapor) require from 4 to 8 minutes   | 
  | Down Time Insufficient?  | time before restarting. Switch off breaker and allow  | 
  | 
  | lamp to cool.  | 
  | 
  | 
  | 
  | 
  | Improper ballasting can cause flickering or erratic  | 
  | Improper Ballast?  | operation. In the   | 
Lamp flickers and goes  | 
  | start to warm up and then extinguish (cycle).  | 
out intermittent or  | 
  | Under certain conditions new lamps may "cycle".  | 
cycling.  | New Lamp?  | Usually after 3 tries to start at 30 to 60 second  | 
  | 
  | intervals, lamps will stabilize and operate satisfactorily.  | 
  | 
  | 
  | 
  | Defective Lamp?  | Replace lamp.  | 
  | 
  | 
  | 