SYMPTOM | PROBLEM | TEST SOLUTION |
|
|
|
Pilot burning; no gas to main burner; Flame height is on ‘HI’; Remote and transmitter ON
Remote receiver | - disconnect switch wires &connect a jumper wire across terminals | |
|
| 1 & 3; if the main burner lights, check the wires for defects and / or |
|
| replace wires. |
Main burner orifice is | - remove stoppage in orifi ce. | |
plugged. |
|
| Faulty thermopile. | - test and replace if required. | |
Pilot goes out while | Gas piping is undersized. | - turn on all gas appliances and see if pilot fl ame fl utters, diminishes or | |
standing; Main |
| extinguishes, especially when main burner ignites. Monitor appliance | |
burner is in ‘OFF’ |
| supply working pressure. | |
position. |
| - | check if supply piping size is to code. Correct all undersized piping. |
Pilot will not light. | No spark at pilot burner | - | check if pilot can be lit by a match |
PILOT |
| - | check that the wire is connected to the spark module. |
BURNER THERMOPILE | - | check batteries. | |
THERMOCOUPLE |
| - | replace the wire if the wire insulation is broken or frayed. |
| - | replace the electrode if the ceramic insulator is cracked or broken. | |
|
| ||
|
| - | replace spark module. |
| Out of propane gas | - | fi ll the tank. |
| Spark gap is incorrect | - | spark gap should be 0.150” to 0.175” (5/32” to 11/64” approx.) from |
|
| the electrode tip and the pilot burner. To ensure proper electrode loca- | |
|
| tion, tighten securing nut (fi nger tight plus 1/4 turn). | |
| No gas at the pilot burner | - | check that the manual valve is turned on. |
|
| - | check the pilot orifi ce for blockage. |
|
| - | call the gas distributor. |
Main burner goes | Pilot flame is not large enough | - | turn up pilot fl ame. |
out; pilot stays on. | or not engulfi ng the thermo- | - replace pilot assembly. | |
| pile |
|
|
| Thermopile shorting | - clean thermopile connection to the valve. Reconnect. | |
|
| - test and replace thermopile if required. | |
| Temperature setting on trans- | - | turn up temperature setting. |
| mitter is satisfi ed |
|
|
Main burner goes out; pilot goes out.
Refer to “MAIN BURNER GOES OUT; PILOT STAYS ON”
Vent is blocked | - | check for vent blockage. |
Vent is | - | check joint seals and installation. |
|
|
|
8” fl exible vent has become | - | |
disconnected from fi replace. |
|
|