Napoleon Fireplaces BGD90NT Using Flexible Vent Components, Horizontal Air Terminal Installation

Models: BGD90PT BGD90NT

1 32
Download 32 pages 7.27 Kb
Page 11
Image 11
USING FLEXIBLE VENT COMPONENTS
INNER
SLEEVE
Figure 21
AIR
TERMINAL
CONNECTOR
HIGH
TEMPERATURE SEALANT
INNER FLEX
LINER
OUTER
FLEX
LINER
DO NOT
CLAMP THE FLEXIBLE
ALUMINIUM LINER.
ROOF SUPPORT

11

USING FLEXIBLE VENT COMPONENTS

Use only approved aluminum flexible liner kits marked:

“Wolf Steel Approved Venting” as identified by the stamp only on the 10” outer liner.

For safe and proper operation of the fireplace, follow the venting instructions exactly.

All inner exhaust and outer intake vent pipe joists may be sealed using either Red RTV high temp silicone seal- ant or Black high temp Mill Pac with the exception of the fireplace exhaust flue collar which must be sealed using Mill Pac (not supplied).

HORIZONTAL AIR TERMINAL INSTALLATION

Note: Direct vent terminals shall not be recessed into a wall or siding.

1.Cut or frame a hole in an exterior wall with a minimum round or square opening of 141/2” W x 141/2” H. Secure the fi restop spacer over the opening to the interior wall.

2.Stretch the 8” diameter fl exible aluminum liner to the re- quired length taking into account the additional length needed for the finished wall surface. Slip the liner a minimum of 2” over the inner sleeve of the air terminal and secure with 6 #8 screws. Apply a heavy bead of the high temperature sealant (W573-0007 not provided).

3.Using the 10” diameter fl exible aluminum liner, slide over the outer combustion air sleeve of the air terminal and secure with 6 #8 screws. Seal as before.

SCREWS

FIGURE 18

#10x2½"

 

 

CAULKING

8"FLEX

PIPE

10" FLEX

2" OVERLAP PIPE

HI-TEMP

SEALANT

TERMINAL

EXTENSION

PLATE

FIGURE 19

8

10

 

10

10

8

 

4.Insert the liners through the fi restop maintaining the required clearance to combustibles. Secure to the exterior wall and make weather tight by sealing with caulking (not supplied).

5.Apply a heavy bead of the high temperature sealant, not supplied with the unit, to the inside of the 8” liner approximately 1” from the end. Slip the liner a minimum of 2” over the fi re- place vent collar and secure with 6 #8 screws.

6.If more than one liner is run we recommend supporting every 5ft.

7.Using the 10” diameter fl exible aluminium liner, apply sealant, slide a minimum of 2” over the fi replace combustion air collar and secure with 6 #8 screws.

VERTICAL AIR TERMINAL INSTALLATION

1.Move the fi replace into position. Figure 20

2.Fasten the roof support to the roof

using the screws provided. The roof support is optional. In this case the venting is to be adequately supported using either an alternate method suitable to the authority having juris- diction or the optional roof support. (Figure 20)

3. Stretch the inner aluminum

ex liner to the required length.

Slip the liner a minimum of 2” over the inner sleeve of the air terminal connector and secure with 6 #8 screws. Seal using a heavy bead of the high temperature sealant. (Figure 21)

4.Repeat using the outer aluminum

fl ex liner. (Figure 21)

5. Thread the air terminal connector

/liner assembly down through the roof. The air terminal must be

located vertically and plumb. Attach the air terminal connector to the roof support, ensuring that the top of the air terminal is 16” above the highest point that it penetrates the

roof. (Figure 22) If the attic space is tight, we recommend threading

the Wolf Steel vent pipe collar or equivalent loosely onto the air terminal assembly as it is passed through the attic.

6. Remove nails from the shingles, above and to the sides of the

chimney. Place the fl ashing over the air terminal connector leaving a min. 3/4” of the air terminal connector showing above the top of the fl ashing. Slide the fl ashing underneath the sides and upper edge

of the shingles. Ensure that c the air terminal connector is properly centred within the

fl ashing, giving a 3/4” margin

 

 

all around. Fasten to the roof.

2”

AIR INLET

Do not nail through the lower

 

BASE

 

 

portion of the fl ashing. Make

 

 

weather-tight by sealing with

 

CAULKING

caulking.

Where

possible,

STORM COLLAR

cover the sides and top

 

 

edges

of

the

fl ashing with

 

 

roofi ng material. (Figure 22)

 

WEATHER

 

SEALANT

7.

Aligning

the

seams

 

 

of the terminal and air

 

 

terminal connector, place the

 

FLASHING

terminal over the air terminal

 

 

connector

making

sure

the

 

 

liner goes

into

the hole

in the terminal.

Secure with the

three screws provided. (Figure 22)

8.Apply a heavy bead of weatherproof caulking 2 inches above the fl ashing. Note: Maintain a minimum 2” space between the air inlet base and the storm collar. Install the storm collar around the air terminal connector and slide down to the caulking. Tighten to ensure that a weather-tight seal between the air terminal connector and the collar is achieved. (Figure 22)

W415-0614 / A / 07.24.07

Page 11
Image 11
Napoleon Fireplaces BGD90NT, BGD90PT manual Using Flexible Vent Components, Horizontal Air Terminal Installation