FIGURE 9
11
USING FLEXIBLE VENT COMPONENTS
USE ONLY WOLF STEEL LTD. 3” / 5” FLEXIBLE VENT COMPONENTS.
ELBOW
SPACERS
!WARNING
Do not allow the 3" flexible vent pipe to bunch up on horizontal or vertical runs and elbows. Keep it pulled tight. A 1” air gap between the 3" and 5" flexible vent pipes all around is required for safe operation. A spacer is required at the start, middle and end of each elbow to ensure this gap is maintained. Spacers are attached to the 3" flexible vent pipe at predetermined intervals to maintain a 1” air gap to the 5" flexible vent pipe. These
spacers must not be removed.
For safe and proper operation of the fireplace, follow the venting instructions exactly.
All 3" flexible vent pipe and 5" flexible vent pipe joints may be sealed using high temperature sealant
Use only approved flexible vent pipe kits marked:
“Wolf Steel Approved Venting” as identified by the stamp only on the 5” flexible vent pipe.
Four inches (4”) is the minimum bend radius allowed for the 5” flexible vent pipe.
HORIZONTAL AIR TERMINAL INSTALLATION
1.Stretch the 3” flexible vent pipe to the required length taking into account the additional length needed for the finished wall surface. Apply a heavy bead of the high temperature sealant
NOTE: If using pipe clamps to connect vent components, 3 screws must also be used to ensure the connection cannot slip off.
2. Using the 5” flexible vent pipe, slide over the outer combustion |
| |
air sleeve of the air terminal and secure with 3 - #8 screws. Seal | FIGURE 10 | |
using high temperature sealant | ||
| ||
3. Insert the flexible vent pipe through the firestop maintaining the |
| |
required clearance to combustibles. Secure the terminal to the |
| |
exterior wall (lettering in an upright, readable position) and make |
| |
weather tight by sealing with caulking (not supplied). |
| |
4. If additional flexible vent pipe is required, couple them together |
| |
as illustrated. The vent system must be supported approximately | FIGURE 11 | |
every 3 feet for both vertical and horizontal runs. Use non- | ||
combustible strapping to maintain the minimum 1” clearance to |
| |
combustibles from the flexible vent pipe. |
|
VERTICAL AIR TERMINAL INSTALLATION
1. Fasten the roof support to the roof using the screws provided. The roof support is optional. In this case the venting is to be adequately supported using either an alternate method suitable to the authority having jurisdiction or the optional roof support. Figure 12.
2.Stretch the 3" flex vent pipe to the required length. Slip the 3" flex vent pipe a minimum of 2” over the inner pipe of the air terminal connector and secure with 3 #8 screws. Seal using a heavy bead of high temperature sealant
FIGURE 12
ROOF SUPPORT
INNER
PIPE
FIGURE 13
AIR
TERMINAL
CONNECTOR
HIGH
TEMPERATURE
NOTE: If using pipe clamps to connect vent
components, 3 screws must also be used to ensure the connection cannot slip off.
3.Repeat using the 5" flex vent pipe, using a heavy bead of high temperature sealant
SEALANT
3” FLEXIBLE VENT PIPE
5” FLEXIBLE VENT PIPE