4
GENERAL INSTRUCTIONS
THIS GAS FIREPLACE SHOULD BE INSTALLED AND SERVICED BY A QUALIFIED INSTALLER to conform with local codes. Installation practices vary from region to region and it is important to know the specifics that apply to your area, for example: in Massachusetts State:
•The fireplace damper must be removed or welded in the open position prior to installation of a fireplace insert or gas log.
•A carbon monoxide detector is required in all rooms containing gas fired appliances.
•The appliance off valve must be a “T” handle gas cock.
•The flexible connector must not be longer than 36 inches.
•The appliance is not approved for installation in a bedroom or bathroom unless the unit is a direct vent sealed combustion product.
•WARNING: This product must be installed by a licensed plumber or gas fitter when installed in the Commonwealth of Massachusetts.
In absence of local codes, install to the current CAN/CGA
The fireplace and its individual shutoff valve must be disconnected from the gas supply piping system during any pressure testing of that system at test pressures in excess of 1/2 psig (3.5 kPa). The fireplace must be isolated from the gas supply piping system by closing its individual manual shutoff valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1/2 psig (3.5 kPa).
When the fireplace is installed directly on carpeting, vinyl tile or other combustible material other than wood flooring, the fireplace shall be installed on a metal or wood panel extending the full width and depth.
GENERAL INFORMATION
FOR YOUR SATISFACTION, THIS FIREPLACE HAS BEEN
RATES AND EFFICIENCIES
| NATURAL GAS | PROPANE GAS |
Altitude | 0 - 4,500* | 0 - 4,500* |
Maximum Input | 6,000 | 6,000 |
Maximum Output | 4,680 | 4,680 |
Efficiency | 78% | 78% |
Minimum Inlet Gas Suppy Pressure | 4.5” Water Column | 11” Water Column |
Maximum Inlet Gas Supply Pressure | 7” Water Column | 13” Water Column |
Manifold Pressure Under Flow Conditions | 3.5” Water Column | 10” Water Column |
*When the fireplace is installed at elevations above 4,500ft, and in the absence of specific recommendations from the local authority having jurisdiction, the certified high altitude input rating shall be reduced at the rate of 4% for each additional 1,000ft.
This fireplace is approved for bathroom, bedroom and
The natural gas model can only be installed in a mobile home that is permanently positioned on its site and fueled with natural gas.
This fireplace may be installed in an aftermarket permanently located, manufactured (mobile) home, where not prohibited by local codes.
This fireplace is only for use with the type of gas indicated on the rating plate. This fireplace is not convertible for use with other gases, unless a certified kit is used.
Expansion / contraction noises during heating up and cooling down cycles are normal and are to be expected.
Purge all gas lines with the glass door of the fireplace open. Assure that a continuous gas flow is at the burner before closing the door.
Objects placed in front of the fireplace must be kept a minimum of 48” from the front face of the unit.
Use only Napoleon® accessories designed for and listed with the model.