37 5/8"
5"
24"
28"
58"
46"
2"
8 7/8"
figure 1
17 3/4"
4" DIA.
7" DIA.
21" 22 1/8"
7/8" | 13 7/8" |
14" |
28" |
General instructions
This gas fireplace should be installed and ser- viced by a qualified installer to conform with local codes. Installation practices vary from region to region and it is important to know the specifics that apply to your area, for example: in Massachusetts State:
•The fireplace damper must be removed or welded in the open position prior to installation of a fireplace insert or gas log.
•A carbon monoxide detector is required in all rooms containing gas fired appliances.
•The appliance off valve must be a “T” handle gas cock.
•The flexible connector must not be longer than 36 inches.
•The appliance is not approved for installation in a bedroom or bathroom unless the unit is a direct vent sealed combustion product.
•WARNING: This product must be installed by a licensed plumber or gas fitter when installed within the commonwealth of Massachusetts.
In absence of local codes, install to the current CAN/CGA
The fireplace and its individual shutoff valve must be discon- nected from the gas supply piping system during any pressure testing of that system at test pressures in excess of 1/2 psig (3.5 kPa). The fireplace must be isolated from the gas supply piping system by closing its individual manual shutoff valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1/2 psig (3.5 kPa).
When the fireplace is installed directly on carpeting, vinyl tile or other combustible material other than wood flooring, the fireplace shall be installed on a metal or wood panel extending the full width and depth.
The optional heat circulating blower is supplied with a cord. If installed, the junction box must be electrically connected and grounded in accordance with local codes. In the absence of local codes, use the current CSA C22.1 canadian elec- trical code in Canada or the ANSI/NFPA 70 national electrical code in the United States.
Purge all gas lines with the glass door of the fireplace open. Assure that a continuous gas flow is at the burner before closing the door.
Under extreme vent configurations, allow several minutes
Provide adequate ventilation and combustion air.
Provide adequate accessibility clearance for servicing and operating the fireplace. Never obstruct the front opening of the fireplace.
Objects placed in front of the fireplace must be kept a minimum of 48” from the front face of the unit.
Minimum clearance to combustible construction from fireplace and vent surfaces:
fireplace framing | - |
0” to | |
fireplace finishing | - 4” from the sides of firebox opening |
| 21 3/4” to top of fireplace opening. |
vent pipe | - 2 inches* |
recessed depth | - 22 1/4 inches |
*The first 2 feet of outer 7 inch diameter vent pipe from the appliance must be wrapped in the 1” thick insulation sleeve (supplied).
General inFORMATION
FOR YOUR SATISFACTION, THIS FIREPLACE HAS BEEN
This fireplace is approved for bathroom, bedroom and bed- sitting room installations and is suitable for mobile home installation. The natural gas model can only be installed in a mobile home that is permanently positioned on its site and fueled with natural gas.
This fireplace may be installed in an aftermarket permanently located, manufactured (mobile) home, where not prohibited by local codes.
This fireplace is only for use with the type of gas indicated on the rating plate. This fireplace is not convertible for use with other gases, unless a certified kit is used.
No external
e l e c t r i c i t y (110 volts or 24 volts) is re- quired for the gas system op- eration.