Napoleon Fireplaces GD82NT, GD82PT Facing and/or finishing material must never, Framing, 59 3/8

Models: GD82PT GD82NT

1 34
Download 34 pages 20.09 Kb
Page 15
Image 15
FRAMING
FIGURE 30

FRAMING

It is best to frame your fireplace after it is positioned and the vent system is installed. Use 2x4’s and frame to local build- ing codes.

Note: In order to avoid the possibility of exposed insulation or vapour barrier coming in contact with the fireplace body, it is recommended that the walls of the fireplace enclosure

15

CLEARANCE TO COMBUSTIBLES

MAINTAIN THESE MINIMUM CLEARANCES TO COM- BUSTIBLES:

Fireplace framing - 0” to stand-offs (top, rear & sides) Fireplace finishing - 4” to sides of fireplace opening.

-21 3/4” to top of fireplace opening.

be “finished” (ie: drywall/sheetrock), as you would finish any other outside wall of a home. This will ensure that clearance to combustibles is maintained within the cavity.

It is not necessary to install a hearth extension, but the fire- place should be raised to be flush with either the hearth or the finished floor.

When roughing in the fireplace, raise the fireplace to accom- modate for the thickness of the finished floor materials, i.e. tile, carpeting, hard wood, which if not planned for will interfere with the removal of the hearth strip, which must be removed to access the firebox.

NON-COMBUSTIBLE FINISHING MATERIAL

 

 

 

Non-combustible

 

 

 

finishing material

 

 

 

(ie: cement board,

21

3

/4"

brick, stone, tile)

 

may be used to fin-

ish the front of the unit.

59 3/8"

Objects placed in front of the fireplace should be kept a mini- mum of 48” away from the front face.

For convenience, the stand-offs have been shipped flat. Before framing, ensure the stand-offs are opened and

4"

24"

4"

 

32"

 

screwed in place.

1"

 

 

 

MIN

 

 

 

44"

 

 

 

1"

29"

"

FIGURE 28

MIN

1/8

 

62

 

IMPORTANT:

The Park Ave. requires a minimum inside enclo- sure height of 72”.

For temperature require- ments, this area must be left unobstructed.

It is recommended that the enclosure be ventilat- ed at the top and bottom to circulate the hot air.

CLEARANCE TO COMBUSTIBLES59 3/8" COMBUSTIBLE Facing and/or finishingoverhang into the fireplaceDo not distort or force the frameManual backgroundManual background

MATERIAL

FIRESTOP

2"

 

SPACER

 

STUD

 

72"

 

2"

STAND OFFManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual background

SPACER

72"

58 1/2"

 

29"

22 1/2"

FIGURE 29

22 1/2"

2 FT.

29" 10" MIN MIN Manual background

FIGURE 31

NON-COMBUSTIBLE

WARNING

Facing and/or finishing

material must never

overhang into the fireplace

opening.

Do not distort or force the frame

kit components.

When using a rough finish materi- al (i.e.; stone), maintain a ¼” - ½” border from the framing components.

W415-0536 / C / 09.06.06

Page 15
Image 15
Napoleon Fireplaces GD82NT Facing and/or finishing material must never, overhang into the fireplace opening, Framing, 59 3/8