BLOWER
INSTALLATION
1.Ensure that the access cover plate has been installed. For location, see Figure 30.
2.Remove the on/off switch bracket and the cover plate below it. The switch spacers and cover plate may now be discarded.
3.Decide which side of the blower housing you prefer the on/off switch to be located on.
SLOT
19
Drywall dust will penetrate into blower bearings causing irrepairable damage and must be prevented from coming into contact with the blower or its compartment.
Any damage resulting from this condition is not covered by the warranty policy.
ADJUSTMENTS
PILOT BURNER ADJUSTMENT
Adjust the pilot screw to provide properly sized flame. Turn in a clockwise direction to reduce the gas flow.
INLET PRESSURE | |||
MANIFOLD TAP | TAP |
| |
|
|
| |
OL |
|
| FIGURE 43 |
|
|
| |
| N |
| O |
HI |
| F | |
O |
| F | |
|
| ||
| TOL | IP |
|
|
|
| |
P |
|
|
|
TOLI |
|
|
|
PILOT SCREW |
|
|
|
FIGURE 44
REMOVED SCREWS
FIGURE 41
4.Remove the 2 screws from the top outer edge of the rear stove panel. The housing is mounted using these two holes, as well as two other holes located in the rear panel. using the same screw holes for one side of the housing.
5.Mount and secure the blower housing using 4 screws. Ensure that the on/off switch wires pass through the ap- propriate slot located on either side of the blower housing.
6.Remove the 2 screws from the side of the blower hous- ing that you want the switch to be located on and resecure the on/off switch.
Because the blower is thermally activated, when turned on, it will automatically start approximately
VENTURI ADJUSTMENT
Remove the 2 screws securing the log support bracket. Natural gas models have air shutters set to 0.375" open (3/8"). Propane models have air shutters set to 0.313" open (5/16"). Closing the air shutter will cause a more yellow flame, but can lead to carboning. The flame may not ap- pear yellow immediately; allow 15 to 30 minutes for the final flame colour to be established. After making adjust- ments replace the log support bracket.
FIGURE 45
Air shutter adjustment must only be done by a qualified gas installer!
RESTRICTING VERTICAL VENTS
Vertical installations may display a very active flame. If this appearance is not desirable, the vent exit must be restricted using the restrictor vent kit,
FIGURE 42pattern and creating a more traditional gentle appearance. Specific instructions are included with the kit.