INSTALLATION AND CLEARANCES
To ensure a safe installation into an existing solid fuel burning fireplace, the following instructions must be carefully followed.
NOTE: Gas control knobs are located in lower front center of base. “OFF/PILOT/ON” Right knob , Thermostat adjustment is the Left knob..
1. Side wall Clearances:
Clearance from the right and left side of the fireplace opening to any adjacent com- bustible wall should not be less than 12”.
2.Ceiling Clearance:
The ceiling height should not be less than 42” from the top of the fireplace opening.
3.Mantel Clearance:
Clearances from top of heater to mantel or mantel supports. See Figure 1.
4.Front Clearances:
No objects should be placed within 24” from the front of the fireplace opening.
MINIMUM FIREPLACE DIMENSIONS FOR CR8T LOG SET MANUFACTURED BY NEW BUCK CORPORATION FOR SOLID FUEL BURNING FIREPLACE OR MASONRY FIREPLACE AND PREFAB OR MANUFACTURED FIREPLACES.
NOTE: When using CR8T log set with the Model 19HS heat shield see page 14 for clearances.
MODEL | HEIGHT OF | WIDTH OF | WIDTH AT | DEPTH OF |
| OPENING | OPENING | REAR | FIREPLACE |
CR8T |
| AT FRONT |
|
|
17” | 24” | 18” | 10” |
NOTE: “Smoke shelves, shields and baffles may be removed if attached by mechanical fasten- ers.”
NOTE: ”Refractory, glass doors, screen rails, screen mesh and
5