Minimum Clearances

The New Buck Corporation Model 80 must be installed in compliance with the instructions contained in this manual.

Clearance from combustible walls and ceilings. (Using single wall chimney connector)

The minimum lateral distance between any part of the room heater and combustible wall is shown in Figures 6 and 7.

FIGURE 6

FIGURE

7

FLOOR PROTECTION

If a freestanding model is to be installed on a combustible floor, a non-combustible pad must be placed below it to protect the floor from burning material from the stove. The pad must be 37" wide by 37 1/2" deep. Floor protector must be 3/8" in minimum thickness, non-combustible material or equivalent.

The unit must be positioned on the pad so that there is a minimum of 16" from the front of the door opening to the front of the pad, and a minimum of 8" measured horizontally from the sides of the fuel loading and ash removal openings to the sides of the pad.

NOTE: For clearance reductions using wall protectors, refer to the NFPA-211 Code.

TOOLS FOR INSTALLATION

Drop Cloth

Electric Drill with 7/32" drill bit 1/2" - 9/16" combination wrench

3/8" magnetic socket chuck adapter, 3/8" wrench (box or socket) or adjustable wrench Socket Set

Tape Measure Pencil Level Screw Driver