IMPROVING CONTROL ACCURACY
The following functions are to assist engineers with machine development, commissioning and troubleshooting.
Using the CheK Control accuracy monitor
I m
READ SP1 OUTPUT PERCENTAGE POWER
SP1.P
To start the monitor select | CHEK | |
ON | ||
| ||
Note: During monitoring either return to normal operation |
|
p r o
Poor control may be due to incorrectly sized heaters. SP1.P (Level 2) constantly displays the output percentage power applied, which at normal setpoint should ideally be within 20 - 80% to achieve stable control.
CONTROL ACCURACY MONITOR | CHEK |
|
This measures the control stability, to within 0.1 °C/°F.
The monitor is started using CheK (Level 3) and the variance (deviation), maximum and minimum temperature
are displayed and constantly updated in | READ | |||||
| ||||||
Temp | Variance |
| ||||
Maximum |
| VAr° | ±0.1° |
| ||
| hi° |
|
|
|
|
|
|
|
|
|
Lo°
Minimum
Time
or remain in program mode. |
| |
To view monitor readings: index to | READ | |
| ||
The lower display will alternate between Var° |
| |
and the variance displayed in degrees (e.g. 0.6) |
| |
Press and hold ✱ and press ▲ once, the lower display will |
| |
alternate between VAr° and the maximum hi° displayed |
| |
in degrees (e.g. 320.3) |
| |
Press and hold ✱ and press ▲ once, the lower display will |
| |
alternate between VAr° and the minimum Lo° displayed |
| |
in degrees (e.g. 319.7) |
| |
CheK oFF stops monitor retaining readings | CHEK | |
| ||
| OFF | |
CheK on resets readings. | CHEK | |
ON | ||
| ||
On |
|
v i n g C o n t r o l A c c u r a c y
15