IMPROVING CONTROL ACCURACY

IMPROVING CONTROL ACCURACY

The following functions are to assist engineers with machine development, commissioning and troubleshooting.

Using the CheK Control accuracy monitor

I m

READ SP1 OUTPUT PERCENTAGE POWER

SP1.P

To start the monitor select

CHEK

ON

 

Note: During monitoring either return to normal operation

 

p r o

Poor control may be due to incorrectly sized heaters. SP1.P (Level 2) constantly displays the output percentage power applied, which at normal setpoint should ideally be within 20 - 80% to achieve stable control.

CONTROL ACCURACY MONITOR

CHEK

 

This measures the control stability, to within 0.1 °C/°F.

The monitor is started using CheK (Level 3) and the variance (deviation), maximum and minimum temperature

are displayed and constantly updated in

READ

 

Temp

Variance

 

Maximum

 

VAr°

±0.1°

 

 

hi°

 

 

 

 

 

 

 

 

 

Lo°

Minimum

Using the CheK Control accuracy monitor Time

or remain in program mode.

 

To view monitor readings: index to

READ

 

The lower display will alternate between Var°

 

and the variance displayed in degrees (e.g. 0.6)

 

Press and hold and press once, the lower display will

 

alternate between VAr° and the maximum hi° displayed

 

in degrees (e.g. 320.3)

 

Press and hold and press once, the lower display will

 

alternate between VAr° and the minimum Lo° displayed

 

in degrees (e.g. 319.7)

 

CheK oFF stops monitor retaining readings

CHEK

 

 

OFF

CheK on resets readings.

CHEK

ON

 

On de-powering CheK resets to oFF and rEAd is zeroed.

 