LEVEL 1 (continued)

LEVEL 1 (continued)

Function

Options [Factory settings] shown in brackets

CYC.T

A - - on.oF 0.1 - 81 sec [20]

 

SP1 proportional cycle-time (see pages 9/10)

 

Determines the cycle rate of the output device for

 

proportional control. Select on.oF for ON/OFF mode.

OFST

[0] to * °C/°F

 

SP1 offset/manual reset

*±50% bAnd. Applicable in proportional and ON/OFF mode with integral disable: Int.t oFF.

SP>LK [oFF] on

Lock main setpoint

Locks the setpoint preventing unauthorised adjustment.

PROGRAMMER SETTINGS (see page 11)

SPRR [0] to 9995 deg/hour

Sets the ramp rate

SPRN on [oFF] hoLd

Switches the ramp on or off, or hold at last ramp value

SOAK [oFF] 0 to 1440 min

Sets the soak time

SP2 OPERATING PARAMETERS (see pages 12/13)
Function

Options [Factory settings] shown in brackets

SET.2

0 to * °C/°F [0]

Adjust SP2 setpoint

*Deviation Alarms DV.hi, DV.Lo, bAnd 25% sensor maximum (see figure 7).

*Full scale alarms FS.hi, FS.Lo

sensor range f/s (see figure 8)

BND.2 0.1 - * °C/°F [2.0 °C/3.6°F]

Adjust SP2 hysteresis or proportional band/gain

(see CyC.2 setting) * 25% sensor f/s

CYC.2 [on.oFF] 0.1–81 seconds

Select SP2 ON/OFF or proportional cycle-time

Select on.oFF for ON/OFF mode, or the cycle rate of SP2 output device for proportional mode.