LEVEL 1 (continued)
Function | Options [Factory settings] shown in brackets |
CYC.T | A - - on.oF 0.1 - 81 sec [20] |
| SP1 proportional |
| Determines the cycle rate of the output device for |
| proportional control. Select on.oF for ON/OFF mode. |
OFST | [0] to * °C/°F |
| SP1 offset/manual reset |
*±50% bAnd. Applicable in proportional and ON/OFF mode with integral disable: Int.t oFF.
SP>LK [oFF] on
Lock main setpoint
Locks the setpoint preventing unauthorised adjustment.
PROGRAMMER SETTINGS (see page 11)
SPRR [0] to 9995 deg/hour
Sets the ramp rate
SPRN on [oFF] hoLd
Switches the ramp on or off, or hold at last ramp value
SOAK [oFF] 0 to 1440 min
Sets the soak time
SP2 OPERATING PARAMETERS (see pages 12/13)
Function | Options [Factory settings] shown in brackets |
SET.2 | 0 to * °C/°F [0] |
Adjust SP2 setpoint
*Deviation Alarms DV.hi, DV.Lo, bAnd 25% sensor maximum (see figure 7).
*Full scale alarms FS.hi, FS.Lo
sensor range f/s (see figure 8)
BND.2 0.1 - * °C/°F [2.0 °C/3.6°F]
Adjust SP2 hysteresis or proportional band/gain
(see CyC.2 setting) * 25% sensor f/s
CYC.2 [on.oFF]
Select SP2 ON/OFF or proportional cycle-time
Select on.oFF for ON/OFF mode, or the cycle rate of SP2 output device for proportional mode.
F u n c t i o n L i s t
17