FUNCTION LIST (Levels 1 to 4)
Note: A Functions Menu is shown on the cover
LEVEL 1
Function Options [Factory settings] shown in brackets
t | SELECT AUTOTUNE |
|
| ||
i s |
|
| |||
TUNE | [oFF] | on ParK At.Sp | |||
L | |||||
| Used to switch the Autotune feature on and off, to | ||||
|
| ||||
n |
| select ParK or Autotune at setpoint. | |||
| ParK temporarily turns the output(s) off. To use select | ||||
o |
| ||||
| ParK and exit program mode. To disable | ||||
|
| ||||
t i |
| program at tunE and select oFF. | |||
SP1 OPERATING PARAMETERS |
| ||||
n c |
| ||||
BAND | 0.1 to * | °C/°F | [10ºC/18ºF] | ||
u |
| SP1 proportional band/Gain or Hysteresis | |||
| * 25% sensor maximum | ||||
F |
| ||||
| Proportional control eliminates the cycling of | ||||
|
|
control. Heater power is reduced, by time proportioning action, across the proportional band.
| Too narrow | Too wide |
|
| |
| (oscillates) | (slow warm up and response) | |||
16 |
|
|
|
| |
increase | BAND | decrease | BAND |
| |
|
|
|
|
|
Function | Options [Factory settings] shown in brackets |
INT.T | oFF 0.1 to 60 minutes [5.0] |
| SP1 integral time/reset |
|
Too short |
| Too long |
(overshoots and oscillates) | (slow warm up and response) | |
DER.T | oFF 1 - 200 seconds [25] |
SP1 derivate time/rate
Suppresses overshoot and speeds response to disturbances
| * | * disturbance | |
Too short | Too long | ||
| |||
(slow warm up and response, | (oscillates and over corrects) | ||
under corrects) |
| ||
DAC | 0.5 - 5.0 x bAnd | [1.5] | |
| SP1 derivative approach control dAC | ||
| Tunes | ||
| operating conditions, by controlling when derivative | ||
| action starts during | ||
| nearer setpoint). |
| |
Too small |
| Too large | |
(overshoots) | (slow stepped warm up) |