Omega Engineering CN9400 specifications Level, F u n c t i o n L i s t

Models: CN9400

1 38
Download 38 pages 50.17 Kb
Page 25
Image 25
IMPORTANT NOTE FOR OEM’s: For safety and to protect settings from tampering

LEVEL 4

Access to level 4 is gained through

VER in level 3.

Press and hold ▲ and ▼

 

for 10 seconds.

 

Enter level 4 at Lock, release ▲ and ▼ together.

Display reads

LOCK

 

 

NONE

Program security using Lock

Select from three Lock options:

Press and hold , press ▲ to index.

LEV.3 locks level 3 and 4 only- Technical Functions.

LEV.2 locks levels 2, 3 and 4 only - Configuration and Technical Functions.

ALL

locks all functions

LOCK

 

 

ALL

Note:

Locked functions and options may be read.

 

Function

Options [Factory settings] shown in brackets

Press ▼ to access following functions

PROG [Auto] StAY

Program mode auto-exit switch

Auto-exit returns display to normal if 60 seconds of key inactivity, select StAY to disable

NO.AL [oFF] on

Disable SP2 alarm annunciator -AL-

Select on to disable -AL-

DIS.S dir 1 to 32 [6]

Display sensitivity

dir = direct display of input

1= maximum, 32 = minimum sensitivity

DER.S 0.1 to 1.0 [0.5]

Derivative sensitivity

F u n c t i o n L i s t