INSTALLATION
The Model CN9400 controller is designed to be mounted in a 1/16 DIN panel
SET-UP
After installation the controller requires programming with the following information:
Type of Input Sensor Operating unit (C or F etc) Type of Output Device Temperature Setpoint
Note: The controller will not be operational until this information is entered.
When the above information has been programmed into the controller it will be operational with the following factory PID (proportional band, integral time, derivative time) settings.
Proportional band/Gain | 10°C/18°F |
Integral time/Reset | 5 mins |
Proportional | 20 secs |
Derivative time/Rate | 25 secs |
DAC Derivative approach control | 1.5 |
OVERVIEW
AUTOTUNE
To precisely control an application the controller will need to be ‘tuned’ using the
During AUTOTUNE the optimum
To ensure good control over a wide range of applications two versions of the Autotune program are provided, TUNE and TUNE AT SETPOINT.
The TUNE method normally achieves the best results. Starting with the load cool, tuning occurs during
The TUNE AT SETPOINT method is used for specialist applications. eg.
The DAC setting is not
O v e r v i e w
3