RAMP-SOAK

RAMP-SOAK

This feature enables the controller to ramp up or down from current temperature to a target setpoint at a pre-determined rate. It then controls at the target setpoint for an adjustable soak period before switching off the heat output.

Set Ramp rate (0 to 9995 deg/hour)

Press ▲ and ▼ buttons for 3 seconds to enter

 

 

PROGRAMMER

Deg.

 

Deg.

Target

Soak

 

 

 

setpoint

 

Ramp °/hour

 

 

 

Ramp °/hour

Target

 

 

 

 

setpoint

 

 

Soak

 

Time

Time

Exit program to enter settings into memory and commence ramp to target setpoint.

P r

program entry point

TUNE

o

 

OFF

Press ▲ to scroll to

SPRR

 

0

Press and hold , then press ▲ or ▼ to scroll to

 

required ramp value in the lower display

 

Set Soak (if required) 0 to 1440 minutes

 

Press ▲ to scroll to

SOAK

--

 

Press and hold , then press ▲ or ▼ to scroll to required soak period in the lower display.

Set Ramp On

(Off) : On : hold

Press ▲ to scroll to

SPRN

 

 

OFF

Press and hold , then press ▲ to select On

 

Notes

In Ramp on configuration, if power is removed from the controller, the Ramp will re-start when power is restored.

The Ramp hold option suspends the ramp at its last value.

If no Soak period has been set, control at target setpoint continues indefinitely.

SP2 deviation alarms follow the ramp setpoint and can be used to alarm “out of limits” ramp rate.