RAMP-SOAK
This feature enables the controller to ramp up or down from current temperature to a target setpoint at a
Set Ramp rate (0 to 9995 deg/hour)
Press ▲ and ▼ buttons for 3 seconds to enter
|
| PROGRAMMER |
Deg. |
| Deg. |
Target | Soak |
|
|
| |
setpoint |
| Ramp °/hour |
|
| |
| Ramp °/hour | Target |
|
| |
|
| setpoint |
|
| Soak |
| Time | Time |
Exit program to enter settings into memory and commence ramp to target setpoint.
P r
program entry point
TUNE
o
| OFF | |
Press ▲ to scroll to | SPRR | |
| 0 | |
Press and hold ✱, then press ▲ or ▼ to scroll to |
| |
required ramp value in the lower display |
| |
Set Soak (if required) 0 to 1440 minutes |
| |
Press ▲ to scroll to | SOAK | |
|
Press and hold ✱, then press ▲ or ▼ to scroll to required soak period in the lower display.
Set Ramp On | (Off) : On : hold |
Press ▲ to scroll to | SPRN |
| |
| OFF |
Press and hold ✱, then press ▲ to select On |
|
Notes
In Ramp on configuration, if power is removed from the controller, the Ramp will
The Ramp hold option suspends the ramp at its last value.
If no Soak period has been set, control at target setpoint continues indefinitely.
SP2 deviation alarms follow the ramp setpoint and can be used to alarm “out of limits” ramp rate.
WARNING
The Soak timer is triggered when the ramp setpoint reaches the target setpoint. If the ramp rate is set too fast for the process, the Soak timer will be triggered before the process temperature reaches the target setpoint.
g r a m m e r
11