CYCLE-TIME SELECTION METHODS

The choice of cycle-time is influenced by the external switching device or load. eg. contactor, SSR, valve. A setting that is too long for the process will cause oscillation and a setting that is too short will cause unnecessary wear to an electro-mechanical switching device.

CYCLE-TIME SELECTION METHODS

The following methods of cycle-time selection may be used:

Autotune calculated

After Autotune has been run and completed the calculated cycle-time can be manually accepted or adjusted to suit the switching device. For selection method see Select Autotune

Calculated Cycle-time.

Pre-select Autotune cycle-time

The controller can be programmed to automatically accept any calculated Autotune cycle-time. For selection method see Pre-Select Automatic Acceptance of Any Autotune

Cycle-time,page 10.

Pre-select before Autotune

The controller can be programmed manually with any cycle-time between 0.1 and 81 sec. This cycle-time will not be changed by any Autotune functions. For selection method see Pre- Select Cycle-time Before Autotune, page 10.

PROPORTIONAL CYCLE-TIME

Factory set

 

 

 

 

 

P

To use the 20 sec factory set cycle-time no action is needed

r

whether autotune is used or not.

 

 

 

 

o p

CYCLE-TIME RECOMMENDATIONS

 

 

 

 

 

 

 

 

 

o

Output

 

Factory

Recommended

 

Load max

 

 

 

 

r

Device

 

Setting

Minimum

 

(resistive)

 

 

 

 

t i

 

 

 

 

 

 

 

Internal relay

 

20 seconds

10 seconds

 

2A/250 Vac

 

rLY/rLY1

 

 

 

o

 

 

 

 

 

 

 

 

 

 

 

 

 

Internal relay

 

20 seconds

10 seconds

 

1A/250 Vac

 

 

 

 

n

rLY2

 

 

 

 

 

 

Solid state

 

20 seconds

0.1 seconds

 

Externally

 

a

drives

 

 

fitted SSR

 

 

 

 

l

SSd/SSd1/SSd2

 

 

 

 

(n/a)

 

 

 

 

 

 

c y

To Select AUTOTUNE CALCULATED CYCLE-TIME

On completion of Autotune enter program mode.

 

 

c l

Select

 

 

 

CYC.T

 

 

 

 

 

e

The controller will display CYC.t and 20 (the factory

 

 

CYC.T

-

setting) in seconds

 

 

 

 

 

 

20

t

 

 

 

 

 

To view the calculated optimum cycle-time press and hold

i

the button then press and hold until indexing stops.

m

The controller will display the calculated cycle-time in the

e

lower display e.g. A 16. This indicates that the calculated

cycle-time is 16 seconds

CYC.T

A16

 

9

Page 13
Image 13