4Termination Locations

A. Vent Termination Minimum Clearances

WARNING

Fire Risk. Explosion Risk.

Maintain vent clearance to combustibles as specified.

Do not pack air space with insulation or other materials.

Failure to keep insulation or other materials away from vent pipe may cause fire.

Measure vertical clearances from this surface.

2FT.

MIN.

GAS DIRECT VENT

TERMINATION CAP

HORIZONTAL

OVERHANG

20 INCHES MIN.

VERTICAL

 

WALL

LOWEST

DISCHARGE

OPENING

X

12

ROOF PITCH

IS X/ 12

H (MIN.) - MINIMUM HEIGHT FROM ROOF TO LOWEST DISCHARGE OPENING

Measure horizontal clearances from this surface. (See Figure 4.4 for specific clearances.)

Figure 4.1 Termination Clearances

A

B

6 in. (minimum) up to 20 in.

18 in. minimum

152 mm/508 mm

457 mm

20 in. and over

0 in. minimum

Gas, Wood or Fuel Oil

Termination Cap

B

A *

Gas

Termination

Cap **

*If using decorative cap cover(s), this distance may need to be increased. Refer to the installation instructions supplied with the decorative cap cover.

**In a staggered installation with both gas and wood or fuel oil terminations, the wood or fuel oil termination cap must be higher than the gas termination cap.

Figure 4.2 Multiple Vertical Termination

Roof Pitch

H (Min.) Ft.

Flat to 6/12

1.0*

Over 6/12 to .......................................................7/12

1.25*

Over 7/12 to 8/12

1.5*

Over 8/12 to 9/12

2.0*

Over 9/12 to 10/12

2.5*

Over 10/12 to 11/12

3.25

Over 11/12 to 12/12

4.0

Over 12/12 to 14/12

5.0

Over 14/12 to 16/12

6.0

Over 16/12 to 18/12

7.0

Over 18/12 to 20/12

7.5

Figure 4.3 Minimum Height from Roof to Lowest Discharge Opening

Figure 4.3 specifies minimum vent heights for various pitched roofs.

8

Quadra-Fire • Topaz • 7009-113 Rev. J • 12/11

Page 8
Image 8
OmniTek 839-1340, 839-1290, 839-1320 owner manual 4Termination Locations, Vent Termination Minimum Clearances