2-77

2 Instructions
CP1E CPU Unit Instructions Reference Manual(W483)
Timer and Counter Instructions
2
TIML/TIMLX
TIML/TIMLX
Applicable Program Areas
Operands
Operand Specifications
Flags
Instruction Mnemonic Variations Function
code Function
LONG TIMER TIML --- 542 TIML(542)/TIMLX(553) operates a decrementing
timer with units of 0.1s.
TIMLX --- 553
Symbol
TIML TIMLX
BCD Binary
Area Step program areas Subroutines Interrupt tasks
Usage OK OK Not allowed
Operand Description Data type Size
TIML TIMLX
D1 Completion Flag WORD UINT 1
D2 PV word DWORD UDINT 2
S SV word DWORD UDINT 2

D1: Completion Flag

D2: PV Word

S: SV Word

The PV and SV can range from #00000000

to #99999999 for TIML(542) and &00000000

to &4294967294 (decimal) or #00000000 to

#FFFFFFFF (hexadecimal) for TIMLX(553).

Note S, S+1, D2 and D2+1 must be in the same
data area.
Area Word addresses Indirect DM addresses Constants CF Pulse bits TR bits
CIO WR HR AR T C DM @DM *DM
D1,D2 OK OK OK OK --- --- OK OK OK --- --- --- ---
SOKOK OK
Name Label Operation
Error Flag P_ER ON if in BCD mode and D2 does not contained BCD data.
ON if in BCD mode and S does not contained BCD data.
OFF in all other cases.
TIML(542)
D1
D2
S
D1: Completion Flag
D2: PV word
S: SV word
TIMLX(553)
D1
D2
S
D1: Completion Flag
D2: PV word
S: SV word
15
D1
0
Completion Flag
Do not use.
D2D2+1
D2 D2+1 is the leftmost 4 digits,
D2 is the rightmost 4 digits
SS+1
SS+1 is the leftmost 4 digits,
S is the rightmost 4 digits