2 Instructions
2-238 CP1E CPU Unit Instructions Reference Manual(W483)
Flags
Function

The data specified in Au/Mi/Md/Dd and the data specified in AD/Su/Mr/Dr are added (+F), subtracted

(-F), multiplied (*F), or divided (/F) as single-precision floating-point data (32 bits: IEEE754) and output

to R+1, R.

+F-F

Name Label Operation

Error Flag P_ER +F
•ON if the augend or addend data is not a number (NaN).
•ON if +∞ and –∞ are added.
-F
•ON if the minuend or subtrahend is not a number (NaN).
•ON if +∞ is subtracted from +∞.
•ON if –∞ is subtracted from –∞.
*F
•ON if the multiplicand or multiplier is not a number (NaN).
•ON if +∞ and 0 are multiplied.
•ON if –∞ and 0 are multiplied.
/F
•ON if the dividend or divisor is not a number (NaN).
•ON if the dividend and divisor are both 0.
•ON if the dividend and divisor are both +∞ or –∞.
OFF in all other cases.
Equals Flag P_EQ •ON if both the exponent and mantissa of the result are 0.
•OFF in all other cases.
Overflow Flag P_OF •ON if the absolute value of the result is too large to be expressed as a 32-bit floating-point value.
•OFF in all other cases.
Underflow Flag P_UF •ON if the absolute value of the result is too small to be expressed as a 32-bit floating-point value.
•OFF in all other cases.
Negative Flag P_N •ON if the result is negative.
•OFF in all other cases.
R+1 R
+
Au
Au+1
Ad
Ad+1
Result (floating-point data, 32 bits)
Augend (floating-point data, 32 bits)
Addend (floating-point data, 32 bits)
R+1 R
–
Mi
Mi+1
Su
Su+1
Result (floating-point data, 32 bits)
Subtrahend (floating-point data, 32 bits)