Reading Pulse Output or High-speed Counter Frequency (C = 00@3 hex)
If C is 00@3 hex, PRV(881) reads the frequency being output from pulse output 0 or 1 or the frequency
being input to high-speed counter 0 and stores it in D and D+1.
0000 or 0001 hex (Reading the frequency of pulse output 0 or 1)
0000 0000 to 0001 86A0 hex (0 to 100,000)
0010 hex (Reading the frequency of high-speed counter 0)
Counter input method: Any input method other than 4× differential phase mode:
Result = 00000000 to 000186A0 hex (0 to 100,000)
Note If a frequency higher than 100 kHz has been input, the output will remain at the maximum value of 000186A0
hex.
Counter input method: 4× differential phase mode:
Result = 00000000 to 00030D40 hex (0 to 200,000)
Note If a frequency higher than 200 kHz has been input, the output will remain at the maximum value of
00030D40 hex.
Pulse Frequency Calculation Methods
The function counts the number of pulses within a fixed interval (the sampling time) and calculates the
frequency from that count. One of the following three sampling times can be selected by setting the
rightmost two digits of C.
Precautions
If the counter is reset when P is 0010 hex (high-speed counter 0) and C is 0013, 0023, or 0033 hex
(sampling method), the data read during the sampling time when the counter was reset will not be
dependable.
Sample program
Sampling time Value of C Description
10 ms 0013 hex Counts the number of pulses every 10 ms. The error is 10% max. at 1 kHz.
100 ms 0023 hex Counts the number of pulses every 100 ms. The error is 1% max. at 1 kHz.
1 s 0033 hex Counts the number of pulses every 1 s. The error is 0.1% max. at 1 kHz.
When CIO 0.00 turns ON in the following
programming example, CTBL(882) registers
a range comparison table for high-speed
counter 0 and starts comparison. When CIO
0.01 turns ON, PRV(881) reads the range
comparison results at that time and stores
them in CIO 0100.
When CIO 1.00 turns ON in the following
programming example, PRV(881) reads the
frequency of the pulse being input to high-
speed counter 0 at that time and stores it as
a hexadecimal value in D200 and D201.
@CTBL
#0000
#0001
D100
0.00
@PRV
#0010
#0002
100
0.01
Range comparison table
registration and comparison start
High-speed counter input 0
High-speed counter input 0
Read range comparison results
PRV
#0010
#0013
D200
1.00
Read input frequency
High-speed counter input
0