2 Instructions
2-210 CP1E CPU Unit Instructions Reference Manual(W483)
Logic Instructions

ANDW/ANDL

Applicable Program Areas
Operands
Operand Specifications
Flags
Instruction Mnemonic Variations Function
code Function
LOGICAL AND ANDW @ANDW 034 Takes the logical AND of corresponding bits in sin-
gle words of word data and/or constants.
DOUBLE LOGICAL AND ANDL @ANDL 610 Takes the logical AND of corresponding bits in
double words of word data and/or constants.
Symbol
ANDW ANDL
Area Step program areas Subroutines Interrupt tasks
Usage OK OK OK
Operand Description Data type Size
ANDW ANDL ANDW ANDL
I1Input 1 WORD DWORD 1 2
I2Input 2 WORD DWORD 1 2
R Result word WORD DWORD 1 2
Area Word addresses Indirect DM addresses Constants CF Pulse bits TR bits
CIO WR HR AR T C DM @DM *DM
I1, I2OK OK OK OK OK OK OK OK OK OK --- --- ---
R---
Name Label Operation
Error Flag P_ER OFF
Equals Flag P_EQ ON when the result is 0.
OFF in all other cases.
Negative Flag P_N ON when the leftmost bit of R is 1.
OFF in all other cases.
I1: Input 1
I2: Input 2
R: Result word
ANDW(034)
I1
I2
R
I1: Input 1
I2: Input 2
R: Result word
ANDL(610)
I1
I2
R