2-61

2 Instructions
CP1E CPU Unit Instructions Reference Manual(W483)
Timer and Counter Instructions
2
Operating Mode
Item TIM/TIMX
(550)
TIMH(015)/
TIMHX(551)
TMHH(540)/
TMHHX(552)
TTIM(087)/
TTIMX(555)
TIML(542)/
TIMLX(553)
Operating mode change PV = 0
Completion Flag = OFF
---
Power interrupt/reset PV = 0
Completion Flag = OFF
---
Execution of CNR(545)/CNRX(547) Binary: PV = FFFF, Completion Flag = OFF
BCD: PV = FFFF or 9999, Completion Flag = OFF
Not applicable
Operation in jumped program sec-
tion (JMP(004)-JME(005))
Operating timers continue timing. Timer status is maintained.
Operation in interlocked program
section (IL(002)-ILC(003))
PV = SV
Completion Flag = OFF
Timer status main-
tained.
PV = SV
Completion Flag =
OFF
Forced set Completion Flag ON ---
PVs Set to 0. ---
Forced reset
Completion
Flags
OFF ---
PVs Reset to SV. Set to 0. ---