2-323

2 Instructions
CP1E CPU Unit Instructions Reference Manual(W483)
High-speed Counter/Pulse
Output Instructions
2
PULSPULS
Applicable Program Areas
Operands
P: Port specifier

T: Pulse type

N and N+1: Number of pulses

The actual number of movement pulses that will be output are as follows:

For relative pulse output, the number of movement pulses = the set number of pulses.

For absolute pulse output, the number of movement pulses = the set number of pulses - the PV.

Operand Specifications
Instruction Mnemonic Variations Function
code Function
SET PULSES PULS @PULS 886 PULS(886) is used to set the pulse output amount (number of out-put pulses).
Symbol
PULS
Area Step program areas Subroutines Interrupt tasks
Usage OK OK OK
Operand Description Data type Size
P Port specifier --- 1
T Pulse type --- 1
N Number of pulses DINT 2
PPort
0000 hex Pulse output 0
0001 hex Pulse output 1
TPulse type
0000 hex Relative
0001 hex Absolute
Area Word addresses Indirect DM addresses Constants CF Pulse bits TR bits
CIO WR HR AR T C DM @DM *DM
P, T --- --- --- --- --- --- --- --- --- OK --- --- ---
N OKOKOKOKOKOKOK OK OK
N: Number of pulse
s
PULS(886)
P
T
N
P: Port specifier
T: Pulse type
N
N+1015Lower word with number of pulsesUpper word with number of pulses