11
ADV/FX/INVERTER-------P00
search        60 cycles
pulse spacing
DOWN  INC      DEC        PORT
ADV/FX/INVERTER-------P00
low battery                        10.5 vdc
cut-out set point
DOWN  INC      DEC        PORT
ADV/FX/INVERTER-------P00
low battery                        12.5 vdc
cut-in set point
DOWN  INC      DEC        PORT
ADV/FX/INVERTER-------P00
adjust                                  120 vac
output voltage
DOWN  INC      DEC        PORT
The search pulse spacing screen adjusts the 
amount of time the FX waits before producing 
additional AC pulses to sense a load. The higher 
the number of cycles, the lower the FX power 
consumption, but the longer it takes before AC
loads are powered. The cycles range from 4 to 
120 cycles (two seconds). Press              to view 
the low battery cut-out screen. 
low battery cut-out establishes when the FX turns 
o  to avoid draining the battery. If an AC source 
is available and AC INPUT is set to DROP,  the FX 
will transfer the AC loads on the FX to the AC 
source. A built-in  ve-minute delay reduces 
nuisance FX shutdowns. This setting’s range is 
between 9.0VDC and 12.0VDC. Press    
to view the next INVERTER screen. 
The low battery cut-in set point determines when 
the FX will turn on after shutting o  due to a low 
battery voltage. A 10-minute  xed delay reduces 
on and o  system cycling. This setting’s range is 
between 10.0 VDC and 14.0 VDC. Press    
to view the adjust output voltage screen. 
A user can adjust the output voltage using this 
screen. Adjustments might be necessary if some 
loads are far away from the FX or if some are 
sensitive to higher voltages. This setting’s range 
is between 110VAC and 125VAC. Press     
to view the next INVERTER screen. 
DOWN
DOWN
DOWN
DOWN