44
Ranking the Slaves:
• From the last screen— ADV/FX/STACK P04—press the <DOWN> soft key twice to get into the power save
level slave adjust only menu. This menu allows you to set the order in which the Slave FXs come “ON”
• Press the <PORT> soft key until P03 is displayed. The FX on Port 03 is the  rst Slave that is in series (“OB
Slave L2”) with the Master. With this FX as the 1st rank Slave, both Legs turn “ON” directly, producing
240VAC without using the FW-X240. If you have a system that is di erent from this example then press
the <PORT> soft key until you get to a Slave FX that is in series (OB Slave L2) with the Master.
• If the screen’s factory setting is not set to 1—the 1st rank Slave—then press the <DEC> soft key until it
becomes 1. Press the <PORT> soft key until P02 appears. If you have a system that is di erent from this
example then press the <PORT> soft key until you get to a Slave FX that is in parallel (OB Slave L1) with
the Master.
• Press the <INC> soft key to change the power save level slave adjust only to 2, which is the 2nd rank Slave.
• Press the <PORT> soft key twice until Port 04 is displayed. If you have a system that is di erent from this
example then press the < PORT> soft key until you get to the next Slave FX that is in series (OB Slave L2)
with the Master.
• Press the <INC> soft key until the setting is 3 for 3rd rank Slave. Any additional FXs in the system can be
programmed by pressing the PORT soft key to get to the next FX and then press <INC> until the setting
is 4 for the 4th rank Slave. Continue this process, making sure each FX has its own slave ranking, until you
have set all FXs.
ADV/FX/STACK----------P04
stack OB Slave L2
phase
DOWN INC DEC PORT
ADV/FX/STACK-----------P04
power save level 1
slave adjust only
DOWN INC DEC PORT
ADV/FX/STACK----------P03
power save level 1
slave adjust only
DOWN INC DEC PORT
ADV/FX/STACK----------P02
power save level 1
slave adjust only
DOWN INC DEC PORT
ADV/FX/STACK----------P02
power save level 2
slave adjust only
DOWN INC DEC PORT
ADV/FX/STACK---------P04
power save level 1
slave adjust only
DOWN INC DEC POR
ADV/FX/STACK----------P04
power save level 3
slave adjust only
DOWN INC DEC PORT
PRESS TWICE