14
ADV/FX/CHARGER---------P00
absorb 01.0 hrs
time limit
DOWN INC DEC PORT
ADV/FX/CHARGER---------P00
oat 13.6 vdc
setpoint
DOWN INC DEC PORT
ADV/FX/CHARGER---------P00
oat 01.0 hrs
time period
DOWN INC DEC PORT
ADV/FX/CHARGER---------P00
re oat 12.2vdc
set point
DOWN INC DEC PORT
The absorb time limit must be long enough for
the batteries to regain 95-100% of their charge.
This time limit can be set between 0 hours and 24
hours using and . The FX auto-
matically reduces this limit when it’s connected to
a partially charged battery. Press to
continue in the CHARGER Menu.
The oat set point is the batteries’  nishing charge
which completes the recharging process. This
setting ranges from 12.0VDC to 15.0VDC. Press
to continue.
The oat time period is the amount of time—from
0 to 24 hours— the recharging process maintains
the oat set point. Larger batteries will probably
require more time than smaller batteries. The
recharging stops when the oat time period is
satis ed. Press to view the next screen.
When the battery voltage falls below the re oat
set point, a  oat cycle recharging starts. This can
act as a maintenance recharging or a recharging
when intermittent DC loads are running and an
AC source is available for recharging. This setting
ranges between 12.0VDC and 13.0VDC. Press
to view the next CHARGER screen.
INC DEC
DOWN
DOWN
DOWN
DOWN