8
To choose your AC input source in the ac transfer
control screen, press or . Press
to view the next screen.
By using and , the ac1/grid menu
sets the maximum current the FX will allow to
be drawn from the grid by either AC loads or the
batteries (during recharging). When this limit is ex-
ceeded, the FX will reduce the amount of charg-
ing current passing through it to the maximum
setting (between 5.0AAC and 60.0AAC). Press
to view the next INPUT screen.
The ac2/gen limit screen sets the maximum
current the FX will allow to be drawn from a
generator by either AC loads or the batteries
(during recharging). When this limit is exceeded,
the FX will reduce the amount of charging cur-
rent passing through it to the maximum setting
(between 2.0AAC and 30.0AAC) to avoid damage
to the generator. Press to view the nal
INPUT screen.
Pressing returns you to the SETUP/FX/
SEARCH screen.
Pressing returns the user to the choose
category screen.
Pressing returns to the MAIN Menu.
.
SETUP/FX/INPUT----------P00
ac transfer Gen
control
DOWN GRID GEN PORT
SETUP/FX/INPUT----------P00
ac1/grid 60.0 aac
limit
DOWN INC DEC PORT
SETUP/FX/INPUT----------P00
ac2/gen 30.0 aac
limit
DOWN INC DEC PORT
SETUP/FX/INPUT----------------
input setup
completed
TOP SETUP MAIN
GRID GEN DOWN
INC DEC
DOWN
DOWN
TOP
SETUP
MAIN