8
To choose your AC input source in the ac transfer
control screen, press or . Press
to view the next screen.
By using and , the ac1/grid menu
sets the maximum current the FX will allow to
be drawn from the grid by either AC loads or the
batteries (during recharging). When this limit is ex-
ceeded, the FX will reduce the amount of charg-
ing current passing through it to the maximum
setting (between 5.0AAC and 60.0AAC). Press
to view the next INPUT screen.
The ac2/gen limit screen sets the maximum
current the FX will allow to be drawn from a
generator by either AC loads or the batteries
(during recharging). When this limit is exceeded,
the FX will reduce the amount of charging cur-
rent passing through it to the maximum setting
(between 2.0AAC and 30.0AAC) to avoid damage
to the generator. Press to view the  nal
INPUT screen.
Pressing returns you to the SETUP/FX/
SEARCH screen.
Pressing returns the user to the choose
category screen.
Pressing returns to the MAIN Menu.
.
SETUP/FX/INPUT----------P00
ac transfer Gen
control
DOWN GRID GEN PORT
SETUP/FX/INPUT----------P00
ac1/grid 60.0 aac
limit
DOWN INC DEC PORT
SETUP/FX/INPUT----------P00
ac2/gen 30.0 aac
limit
DOWN INC DEC PORT
SETUP/FX/INPUT----------------
input setup
completed
TOP SETUP MAIN
GRID GEN DOWN
INC DEC
DOWN
DOWN
TOP
SETUP
MAIN