ADV/FX/AUX---------------P00
aux output Remote
function
DOWN INC DEC PORT
From the remote aux output function screen,
press . This will bring up the
rst of several screen used to adjust which ever
mode you have chosen for the AUX function.
ADV/FX/AUX---------------P00
genalert 11.5vdc
on setpoint
DOWN INC DEC PORT
The genalert on setpoint screen shows the
voltage—whose range is between 10.0 VDC and
14.0VDC, adjusted with and —
that energizes the AUX in genalert mode.
Press to view the genelert on delay
screen.
ADV/FX/AUX---------------P00
genalert 11.5 vdc
on delay
DOWN INC DEC PORT
The genalert on delay is the amount of time
the battery voltage must remain below the
genalert set point before the AUX is energized.
This allows for brief periods of heavy load usage
and has a range of 0-240 minutes in one minute
increments, adjustable with and .
Press to bring up the genalert o
setpoint screen.
ADV/FX/AUX----------------P00
genalert 14.0 vdc
o setpoint
DOWN INC DEC PORT
In genalert mode, the AUX de-energizes when
the genalert o setpoint is reached. This setpoint’s
range is between 12.0VDC and 18.0VDC and is
adjusted using and . Press
to view the genalert o delay screen.