From the  remote aux output function screen, 
press               .  This will bring up the 
 rst of several screen used to adjust which ever 
mode you have chosen for the AUX function.
ADV/FX/AUX---------------P00
genalert                                     11.5vdc
on setpoint
DOWN    INC     DEC      PORT
The genalert on setpoint screen shows the 
voltage—whose range is between 10.0 VDC and 
14.0VDC, adjusted with               and               —
that energizes the AUX in genalert mode.
Press               to view the genelert on delay
screen.
ADV/FX/AUX---------------P00
genalert                                    11.5 vdc
on delay  
DOWN    INC     DEC      PORT
The genalert on delay is the amount of time
the battery voltage must remain below the 
genalert set point before the AUX is energized. 
This allows for brief  periods of heavy load usage 
and has a range of 0-240 minutes in one minute 
increments, adjustable with                and               .                      
Press                to bring up the genalert o  
setpoint screen. 
ADV/FX/AUX----------------P00
genalert                                    14.0 vdc
o  setpoint
DOWN    INC     DEC      PORT
 In genalert mode, the AUX de-energizes when
the genalert o  setpoint is reached. This setpoint’s 
range is between 12.0VDC and 18.0VDC and is 
adjusted using               and               .  Press                
to view the genalert o  delay screen. 