54
12 VDC System DEFAULT MINIMUM MAXIMUMFloat Voltage 13.6V 12V 15V
Absorb Voltage 14.4V 13V 16V
EQ Voltage 14.4V (24VDC Grit-Tie=29.2) 14V 17V
ReFloat 12.5V 11V 13V
LBCO 10.5V 9V 12V
LBCI 12.5V 10V 14V
Sell RE 13V 10V 15V
Gen Alert
O Set Point 14V 12V 18V
On Set Point 11V 10V 14V
Load Shed O Set Point 11V 10V 14V
Vent Fan ON Set Point 13V 10V 16V
Diversion ON Set Point 14.6V 12V 16V
Absorb Time 1.0 hours 0.0 hours 24.0 hours
EQ Time 1.0 hours 0.0 hours 24.0 hours
Float Time 1.0 hours 0.0 hours 24.0 hours
AC2/Gen Transfer Delay
(Cycles for AC)
60 cycles*
(*20 for Grid-Tie)
0 cycles 240 cycles
Search 6 0 50
Grid Lower Limit 108V 40V 115V
Grid Upper Limit 140 80V 220V
Grid Upper Limit 140V 130V 150V
Grid Connect Delay .5 min .2 min 15.0 min
DROP or USE USE N/A N/A
Charger OFF/AUTO/ON AUTO
AUX Output Option COOL FAN
Gen Alert ON Delay 4 min 0 min 240 min
Gen Alert OFF Delay 9 min 0 min 240 min
Vent Fan OFF Delay 5 min 0 min 30 min
Gen Window Lower Limit 108V 40V 115V
Gen Upper Window Limit 140V 130V 150V
AC1/Grid Transfer Delay 6 Cycles of AC 0 Cycles of AC 240 Cycles of AC
Set AUX Control AUTO
Search Pulses 8 2 20
Search Pulse Spacing 60 Cycles Ac 4 Cycles AC 120 Cycles AC
Stacking Phase 1 or 2 phase
InPut Select Master Gen
Charge Rates
Vented 24 & 48 VDC 9 AAC 0 AAC 10 AAC
Vented 12 VDC 6 AAC 0 AAC 7 AAC
Sealed 24 & 48 VDC 5 AAC 0 AAC 7 AAC
Sealed 12 VDC 5 AAC 0 AAC 6 AAC
Grid Input Settings
Set AC Input Size
Mobile 28 Amp 5 Amp 30 Amp
Non-Mobile U.S. 48 Amp 5
Grid-Tie 50 Amp
Gen Input Settings
Mobile 28 Amp 2Amp 30 Amp
Non-Mobile U.S. 48 Amp 2 Amp 60 Amp
Grid-Tie 50 Amp
Set VAC 120V (230V Export) 110V GT (210V Export,
105V O -Grid and Mobile)
125V (240V Export)
FX Default Values (subject to change with FX upgrades)
Correction Factor
•24VDC: Multiply 12VDC values by 2 •32VDC: Multiply 12VDC values by 2.64 •48VDC: Multiply 12VDC values by 4