Panasonic 8900 SH Series 8900SH Control Panel, Operation And Installation Manual, Section

Models: 8900 SH

1 37
Download 37 pages 47.81 Kb
Page 20
Image 20
OTHER IMPORTANT ITEMS:

Series 8900SH Control Panel

Operation And Installation Manual

90This code, and the ones that follow, are all time clocks, providing elapsed running time since the boilers were originally installed. Press Code 90 to start the display.

91This code allows you to pick which boiler to check the elapsed time on. To view boiler # 5 enter 91, and then 5. Then the panel will automatically go to code 92.

92This code shows the total number of hours and minutes that a boiler has run since it was installed up to a maximum of 23 hours, 59 minutes. When 24 hours have accumulated one day is automatically added to code 93. Press # to view code 93.

93This code shows the total number of days a boiler has run since it was installed up to a maximum of 9999.

You can clear the accumulated time for all boilers and start over at time zero by entering code 91, then entering 99, and pressing the # sign. This is useful when boiler maintenance is planned. By zeroing out the elapsed time after a maintenance procedure, you now have a timer that can count upwards to the point when maintenance must be done again.

NOTE: WHEN THE KEYBOARD LOCKED, ALL CODES CAN STILL BE VIEWED.

OTHER IMPORTANT ITEMS:

The panel has two rechargeable batteries that will reain all stored information for 30 days if the power goes out for any reason.

If the control panel fails for any reason, or is accidentally unplugged, the boilers automatically come on and are then controlled by their own high limit switches. Thus, the system will never be out of heat because of panel failure.

Section 6

Monitoring Codes

Page 20
Image 20
Panasonic 8900 SH Series 8900SH Control Panel, Operation And Installation Manual, Section, Monitoring Codes