Panasonic 8900 SH Press, = Entry Code, ENTRY CODE 28 OUTSIDE DESIGN TEMPERATURE SETTING, Section

Models: 8900 SH

1 37
Download 37 pages 47.81 Kb
Page 26
Image 26
PRESS

Series 8900SH Control Panel

Operation And Installation Manual

ENTRY CODE 27: DESIGN RETURN WATER TEMPERATURE SETTING

PRESS

2

+

7

= ENTRY CODE

 

 

 

 

 

 

 

 

ENTER YOUR CHOICE

 

 

 

 

 

 

 

1

 

8

 

 

 

 

 

 

 

 

 

 

0

PRESS

#

= SAVE KEY, TO SET DESIGN RETURN WATER TEMPERATURE.

THE AVAILABLE TEMPERATURE RANGE IS +100°F TO +225°F

This sets the Design Return Water Temperature. It is important to set it correctly because many of the panel’s calculations are based on this figure. Usually the system design engineer will have already calculated this. However, if you do not know the proper temperature simply use 180°F.

ENTRY CODE 28: OUTSIDE DESIGN TEMPERATURE SETTING

PRESS

2

+

8

= ENTRY CODE

ENTER YOUR CHOICE

-

1

0

PRESS

#

= SAVE KEY, TO SET OUTSIDE DESIGN TEMPERATURE.

THE AVAILABLE TEMPERATURE RANGE IS - 20°F TO +50°F

This code sets the Design Outside Temperature, which is the average coldest temperature your geographic area is expected to experience. The correct figure can be found by calling a local heating contractor or your mechanical engineer.

To enter a number below 0°F degrees, press any two keys side by side at the same time to set the display to a negative number, then enter the temperature.

Section 8

Entry Code Details

Page 26
Image 26
Panasonic 8900 SH Press, = Entry Code, ENTRY CODE 28 OUTSIDE DESIGN TEMPERATURE SETTING, Series 8900SH Control Panel