every 1°F the outside temperature drops, the Return Water Line temperature is increased 1°F. If the ratio is set at 1.50, the Return Water Line will increase 1.5°F for every 1°F drop in outside temperature.
THE FORMULA BELOW WILL HELP YOU DETERMINE THE INITIAL RATIO SETTING.
Outdoor Reset Ratio Formula: |
| |
Design Return Water Temperature – Minimum Return Water Temperature | = Outdoor Reset | |
Outside Shutdown Temperature – Outside Design Temperature | Ratio | |
Example: |
|
|
180°F - 100°F = | 80°F = 1.14 Reset Ratio |
|
60°F - | 70°F |
|
ENTRY CODE 24: RATE OF CHANGE FACTOR
PRESS 2 + 4 = ENTRY CODE
ENTER YOUR CHOICE |
|
|
|
| .1 |
0
PRESS
#
= SAVE KEY, FOR A RATE OF CHANGE FACTOR OF .10.
THE AVAILABLE RANGE IS FROM .01 TO 2.00
This code allows you to set the speed of the counter that was explained in code 17. The Rate of Change Factor directly influences how fast or slow boilers are brought on line when heat is called for. If boilers are brought on line too quickly, a waste of fuel can result due to too many boilers running and
ENTRY CODE 26: NUMBER OF BOILERS TO BE CONTROLLED
PRESS | 2 | + | 6 | = ENTRY CODE | |||||
|
|
|
|
|
|
|
| ||
ENTER YOUR CHOICE |
|
|
|
|
| ||||
|
|
|
| 2 | |||||
|
|
|
|
|
|
|
|
|
|
4
PRESS
#
= SAVE KEY, TO CONTROL 24 BOILERS.
THE AVAILABLE RANGE IS FROM 1 TO 24
Section 8 | Entry Code Details |