ENTRY CODE 24: RATE OF CHANGE FACTOR

Series 8900SH Control Panel

Operation And Installation Manual

every 1°F the outside temperature drops, the Return Water Line temperature is increased 1°F. If the ratio is set at 1.50, the Return Water Line will increase 1.5°F for every 1°F drop in outside temperature.

THE FORMULA BELOW WILL HELP YOU DETERMINE THE INITIAL RATIO SETTING.

Outdoor Reset Ratio Formula:

 

Design Return Water Temperature – Minimum Return Water Temperature

= Outdoor Reset

Outside Shutdown Temperature – Outside Design Temperature

Ratio

Example:

 

 

180°F - 100°F =

80°F = 1.14 Reset Ratio

 

60°F - (-10°F)

70°F

 

ENTRY CODE 24: RATE OF CHANGE FACTOR

PRESS 2 + 4 = ENTRY CODE

ENTER YOUR CHOICE

 

 

 

 

.1

0

PRESS

#

= SAVE KEY, FOR A RATE OF CHANGE FACTOR OF .10.

THE AVAILABLE RANGE IS FROM .01 TO 2.00

This code allows you to set the speed of the counter that was explained in code 17. The Rate of Change Factor directly influences how fast or slow boilers are brought on line when heat is called for. If boilers are brought on line too quickly, a waste of fuel can result due to too many boilers running and short-cycling. Too long a count between boilers may result in unsatisfactory heat to the building. TRIAD recommends an initial setting of .10. The lower the factor, the longer (slower) the response time of the boilers, and the higher the factor, the shorter (faster) the response time.

ENTRY CODE 26: NUMBER OF BOILERS TO BE CONTROLLED

PRESS

2

+

6

= ENTRY CODE

 

 

 

 

 

 

 

 

ENTER YOUR CHOICE

 

 

 

 

 

 

 

 

 

2

 

 

 

 

 

 

 

 

 

 

4

PRESS

#

= SAVE KEY, TO CONTROL 24 BOILERS.

THE AVAILABLE RANGE IS FROM 1 TO 24

Section 8

Entry Code Details

Page 25
Image 25