SERIES 8900SH SPECIFICATIONS:

Series 8900SH Control Panel

Operation And Installation Manual

SERIES 8900SH SPECIFICATIONS:

Input Voltage

9.8 vac, 50/60 Hz, max input 35 vac with transient/surge protection

 

 

Avg. Power Consumption

3VA

 

 

Battery Protected Memory

8K RAM

 

 

CPU

Industry standard Z80, 4MHz

 

 

Time Clock

Internal crystal based clock

 

 

Operating System Memory

8K EPROM

 

 

Serial Interface

1200 Baud standard TTL signal level. Can be interfaced with modem

 

or direct connect to IBM compatible PC

Sensor Input Channels

Six

 

Sensor input Range

Voltage input of 1.9VDC is read at a value of –55 by the controller.

 

Voltage input of 3.1VDC is read as a value of 200. If an input is

 

shorted to common, the controller will read –40 at the input. If input

 

is open, the controller will read 230.

Sensor Accuracy

Within + or – 1 degree Fahrenheit

 

 

Sensor Type

Solid-state linear sensing

 

 

Output Channels

Up to 24

 

 

Output Capacity

30VA, 24VAC

 

 

Relay Type

Coil 12VDC / “Dry Contact”

 

 

All Other Components

5VDC

 

 

Wiring

Multiconductor 18 AWG thermostat wire is recommended to wire

 

sensor inputs and control outputs. Maximum length of wire from

 

control panel to sensor is 300 feet.

Batteries

Two 1.2V sealed nickel-cadmium rated at 720 hrs. Standard charge

 

15 hrs at 18mA.

Display

Light Emitting Diodes

 

 