15.1.1Relationship between the condition of the air conditioner and pressure and electric current

Condition of the

 

Cooling Mode

 

 

 

 

air conditioner

Low Pressure

High Pressure

Electric current during operation

 

 

 

 

Insufficient refrigerant

Ô

Ô

Ô

(gas leakage)

 

 

 

Clogged capillary tube or

Ô

Ô

Ô

strainer

 

 

 

Short circuit in the indoor unit

Ô

Ô

Ô

 

 

 

 

Heat radiation deficiency

Ò

Ò

Ò

of the outdoor unit

 

 

 

Inefficient compression

Ò

Ô

Ô

 

 

 

 

• Carry out the measurement of pressure, electric current, and temperature fifteen minutes after an operation is started.

15.1.2Diagnosis methods of a malfunction of a compressor

Nature of fault

Insufficient compressing of a compressor

Locked compressor

Symptom

Electric current during operation becomes approximately 20% lower than the normal value.

The discharge tube of the compressor becomes abnormally hot (normally 70°C to 90°C).

The different between high pressure and low pressure becomes almost zero.

Electric current reaches a high level abnormally, and the value exceeds the limit of an ammeter. In some cases, a breaker turns off.

The compressor has a humming sound.

54

Page 54
Image 54
Panasonic CS-C18KKS, CU-C18KKS, CU-C24KKS, CS-C24KKS Diagnosis methods of a malfunction of a compressor, High Pressure