2-2-2. Outdoor Unit
Outdoor Unit
Control PCB |
|
|
| ||
|
|
|
|
|
|
| Part No. |
|
| ||
| Controls |
|
| Microprocessor | |
| Control Circuit Fuse |
|
| 125V 25A | |
|
|
|
|
| |
Compressor |
|
|
| ||
|
|
|
|
|
|
| Type |
|
| DC Rotary (Hermetic) | |
| Compressor Model / Nominal Output |
|
| G4C090LU1ER / 900W | |
| Compressor Oil ... Amount | Pints (cc) | FV50S ... 0.68 (320) | ||
| Coil Resistance (Ambient Temp. 68 °F (20 °C)) Ohm | U - V : 0.81 | |||
|
|
|
|
| V - W : 0.81 |
|
|
|
|
| W - U : 0.81 |
| Safety Device |
|
|
| |
|
| CT (Peak current | Yes | ||
|
| Compressor Discharge Temp. Control | Yes | ||
|
| Operation | Yes | ||
|
| Overload Relay |
| Model | |
|
|
| Operation Temp. | Open : 239 °F (115 °C), Close : 203 °F (95 °C) | |
| Run Capacitor |
| Micro F | - | |
|
|
|
| VAC | - |
| Crankcase Heater |
|
| 115V 20W | |
|
|
|
|
|
|
Fan |
|
|
| ||
|
|
|
|
|
|
| Type |
|
| Propeller | |
| Q'ty ... Dia. | inch (mm) | 1 ... | ||
|
|
|
|
| |
Fan Motor |
|
|
| ||
|
|
|
|
|
|
| Type |
|
| DC Motor | |
| Model ... Q'ty |
|
| ||
| No. of Poles |
|
| 8 | |
| Rough Measure RPM (Cool / Heat) |
|
| 750 / 750 | |
| Nominal Output |
| W | 50 | |
| Coil Resistance |
| Ohm | RED - WHT : 77.5 | |
| (Ambient Temp. 68 °F (20 °C)) |
|
| WHT - BLU : 77.5 | |
|
|
|
|
| BLU - RED : 77.5 |
|
|
|
|
|
|
| Safety Device |
|
|
| |
|
| Type |
|
| Internal Controller |
|
| Over- Current Protection |
|
| Yes |
| Run Capacitor |
| Micro F | - | |
|
|
|
| VAC | - |
|
|
|
|
|
|
Heat Exchanger Coil |
|
|
| ||
|
|
|
|
|
|
| Coil |
|
| Aluminum Plate Fin / Copper Tube | |
| Rows |
|
| 2 | |
| Fins per inch |
|
| 18.1 | |
| Face Area |
| ft2 (m2) | 3.95 (0.367) | |
|
|
|
| ||
External Finish |
|
| Acrylic | ||
|
|
|
|
|
|
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
15