9. TROUBLESHOOTING (BEFORE CALLING FOR SERVICE)

9-1. Precautions before Performing Inspection or Repair

After checking the self-diagnostics monitor, turn the power OFF before starting inspection or repair.

High-capacity electrolytic capacitors are used inside the outdoor unit controller (inverter). They retain an electrical charge (charging voltage DC 310V) even after the power is turned OFF, and some time is required for the charge to dissipate. Be careful not to touch any electrified parts before the controller LED (red) turns OFF.

If the outdoor controller is normal, approximately 30 seconds will be required for the charge to dissipate. However, allow at least 5 minutes for the charge to dissipate if there is thought to be any trouble with the outdoor controller.

9-2. Method of Self-Diagnostics

Follow the procedure below to perform detailed trouble diagnostics.

NOTE

1:If the operation lamp blinks every 0.5 seconds immediately when the power is turned ON, there is an external ROM (OTP data) failure on the indoor circuit board, or a ROM socket insertion problem, or the ROM has not been installed.

2:The failure mode is stored in memory even when the power is not ON. Follow the procedure below to perform diagnostics.

PROCEDURE

After turning on power to the air conditioner, use the remote controller and follow the steps below to execute self-diagnostics.

Step 1: Press and hold the remote controller QUIET button and 1 HR TIMER button. Then, press and hold the ACL (reset) button with a pointed object such as the tip of a pen. After 5 seconds, release ACL button first, then release QUIET and 1 HR TIMER buttons, "oP-1" (test run) appears, blinking in the remote controller clock display area.

Step 2: Next, press the 1 HR TIMER button once to change the display from "oP-1" to "oP-3" (self-diagnostics). (The display continues to blink.)

Step 3: Finally press the ON/OFF button to engage self-diagnostics mode.

The self-diagnostics function utilizes the 3 indicator lamps on the main unit, in combinations of ON lamps, blinking lamps, and OFF lamps, to report the existence of sensor trouble or a protective operation. (The lamps blink or remain ON for 5 seconds, then turn OFF for 2 seconds.) Self-diagnostics is completed when the buzzer sounds 3 short beeps.

A maximum of 3 self-diagnostics reports are displayed, for 5 seconds each, beginning with the most recent report. Following this display the lamps turn OFF. In order to view the self-diagnostics results again, press the ON/OFF button again.

The 3 lamps remain OFF if no trouble has occurred.

<IMPORTANT> After self-diagnostics is completed, be sure to press the ACL (reset) button to return to normal mode. The air conditioner will not operate if this is not done.

QUIET button

<Clock display > Test run mode

Self-diagnostics mode

ON/OFF operation button

1HR.

TIMER button

ACL (Reset) button

47

Page 47
Image 47
Panasonic CU-KS24NKUA Troubleshooting Before Calling for Service, Precautions before Performing Inspection or Repair

CU-KS24NKUA, CS-KS24NKU, CU-KS24NKU specifications

The Panasonic CU-KS24NKUA, CU-KS24NKU, and CS-KS24NKU are a part of the company’s advanced air conditioning lineup, known for their efficient performance and user-friendly features. Designed to provide optimal cooling while ensuring energy efficiency, these models cater to both residential and commercial spaces, making them an ideal choice for various settings.

One of the standout features of the Panasonic CU-KS24NKUA and its counterparts is their inverter technology. This innovative approach allows the air conditioning units to adjust their cooling capacity based on the room's temperature, thus ensuring that they operate at peak efficiency. By minimizing energy consumption during low demand, the units not only lower electricity bills but also reduce environmental impact.

The CU-KS24NKU series is equipped with a powerful compressor that delivers high cooling performance, capable of rapidly cooling spaces even in extreme heat conditions. Additionally, with a robust SEER (Seasonal Energy Efficiency Ratio) rating, these models rank among the top in energy savings, making them suitable for energy-conscious consumers.

Continuous airflow is vital for maintaining a comfortable indoor environment, and the CS-KS24NKU includes features that enhance air circulation. Utilizing a multi-directional airflow system, these units ensure that cool air is distributed evenly throughout the room, minimizing hot spots and maximizing comfort.

Another significant characteristic of the Panasonic air conditioners is their silent operation. Designed with low noise levels in mind, these units ensure that cooling does not come at the expense of peace and quiet, making them perfect for bedrooms or offices where a tranquil environment is essential.

In addition to performance, the Panasonic CU-KS24NKUA, CU-KS24NKU, and CS-KS24NKU are also equipped with comprehensive filtration systems. These filters capture dust, allergens, and pollutants, promoting better air quality within indoor spaces. This is particularly beneficial for individuals with allergies or respiratory concerns.

Remote control and smart capabilities are also integral features, allowing users to operate and schedule their air conditioner from anywhere within the home. This convenience adds a layer of flexibility to managing indoor climates, especially in today's fast-paced world.

In summary, the Panasonic CU-KS24NKUA, CU-KS24NKU, and CS-KS24NKU air conditioning units represent a perfect blend of advanced technology, energy efficiency, and user comfort. Their inverter technology, effective air distribution, quiet operation, and enhanced air filtration make them a valuable addition for those seeking reliable climate control while prioritizing sustainability and comfort.