Panasonic CU-KS24NKUA Service Valve Connections, Remote Controller Installation Position, Table

Models: CU-KS24NKUA CS-KS24NKU CU-KS24NKU

1 122
Download 122 pages 21.06 Kb
Page 119
Image 119
Service Valve Connections

Service Valve Connections

a)Temporary connection:

Screw in 3 – 5 turns by hand. (Fig. 60c)

b)To fasten the flare nuts, apply specified torque as Table 9 and Fig. 60d.

Table 9

Tube Dia.

Nut

Tightening Torque

 

 

 

1/4" (6.35 mm)

21/32" (17 mm)

Approx. 120 – 160 lbs·in (140 – 180 kgf·cm)

 

 

 

3/8" (9.52 mm)

7/8" (22 mm)

Approx. 300 – 360 lbs·in (340 – 420 kgf·cm)

 

 

 

1/2" (12.70 mm)

1-1/32" (26 mm)

Approx. 430 – 480 lbs·in (490 – 550 kgf·cm)

 

 

 

5/8" (15.88 mm)

1-5/32" (29 mm)

Approx. 590 – 710 lbs·in (680 – 820 kgf·cm)

 

 

 

Fig. 60c

CAUTION

Torque wrench

Fig. 60d

Be sure to tighten the flare nut using the prescribed torque.

If the nut is over- tightened, refrigerant leakage may occur.

7. Remote Controller Installation Position

The remote controller can be operated from either a non-fixed position or a wall-mounted position.

To ensure that the air conditioner operates correctly, do not install the remote controller in the following places:

In direct sunlight

Behind a curtain or other place where it is covered

More than 26' (8 m) away from the air conditioner

In the path of the air conditioner’s airstream

Where it may become extremely hot or cold

Where it may be subject to electrical or magnetic interference

Where there is an obstacle between the remote con- troller and the air conditioner (since a check signal is sent from the remote controller every 5 minutes)

7-1. Mounting on a Wall

Before mounting the remote controller, press the ON/OFF operation button at the mounting location to make sure that the air conditioner operates from that location. The indoor unit should make a beeping sound to indicate that it has received the signal.

Remote control holder

Fig. 60c Press

Set in place

Mounting screws 5/32 x 5/8" (4 x 16 mm)

(Included)

Rear side

Hole

To prevent loss of the remote controller, you can connect the remote controller to the holder by passing a string through the remote controller and attachment hole.

To take out the remote controller, pull it forward.

Fig. 61

27

Page 119
Image 119
Panasonic CU-KS24NKUA Service Valve Connections, Remote Controller Installation Position, Table, d, Mounting on a Wall