6.5 GT11
6.5.1 General Specifications (GT11)
Item
Specifications
Rated voltage
24 V DC
Operating voltage range
21.6 to 26.4 V DC
Power consumption
2.4 W or less (100 mA or less) Note1)
Ambient temperature
0 to +50
°
C Note2)
Ambient humidity
20 to 85% RH (at 25
°
C, non-condensing)
Storage temperature
-20 to +60
°
C
Storage humidity
10 to 85% RH (at 25 °C, non-condensing)
Breakdown voltage Between [power supply terminals] and [case]
500 V AC for 1 minute, Cutoff current 10mA (at default setting)
Insulation resistance
Between [power supply terminals] and [case]
100 MΩ or more, 500 V DC, measured with megohmmeter (at default
setting)
Vibration resistance
10 to 55 Hz (1-minute cycle)
Amplitude: 0.75 mm,
10 min on 3 axes
Shock resistance
98 m/s2 or more,
4 times on 3 axes
EC Directive applicable
EMC Directive: EN61000-6-2, EN61000-6-4
Noise immunity 1000 V [P-P] or more, Pulse width 50 ns, 1µs between power supply
terminals (based on in-house measurements)
Note3)
Protective construction
IP65 (Initial value, evaluated by us)
Dustproof and drip-proof from front panel only (packing used on panel
contact surface)
Note4)
Weight
Approx. 230 g
Note1) When connecting the FP programmer II to the TOOL port, it is 150 mA or less.
Note2) When connecting the FP programmer II or C-NET adapter to the TOOL port, the usable range is
0 to +45 °C.
Note3) When using our exclusive cable.
Note4) When reattaching, replace waterproof packing.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net