3.6.4 Dead Battery Mark 3.6.5 Time for Replacement of Battery 3.6.6 Replacement of Front Panel Protective Sheet
If the battery voltage drops too low, the battery mark is displayed at the bottom right of the GT screen.
When the battery voltage drops
It can be specified in the GTWIN configuration settings, whether or not the dead battery mark is
displayed .
Note:
If the battery voltage drops too low, the BAT LOW flag of the basic communication area map goes on. If
the battery has run down completely, the BAT flag of the basic communication area map goes on.
Please be aware that the BAT flag goes on the first time that the power supply is turned on after the unit
is purchased.
* The BAT and BAT LOW flags in the basic communication area map activate in the both cases that the
battery error display is set to “On” and “Off”.
When replacing the backup battery, turn on electricity for the time for energization, and replace the
battery with a new one within one minute after turning off the power supply.
If the battery is not replced within the time for replacement, the saved data will be lost.
Time for energization
Time for replacement
1 min. or more (10 min. or more for GT32)
Within 1 min.
About the front panel protective sheet
Use the separately-sold protective sheets to protect the touch panel surface and to keep it clean.
Replacing the front panel protective sheet (For the type with protective film)
Follow the steps below to replace the sheet:
1. Peel off the seal from the provided protector sheet and attach it to the unit.
Take out one of the replacement front panel protective sheets and peel off the seal with the shiny side.
When attaching the sheet, align the adhesive edges with the front of the GT. Finish by peeling off the
thin film attached to the top of the front panel protective sheet.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net