6.8.4 Interface Specifications (GT32)
Interface for connecting PLC/External devices
- COM port
Item
Specifications
AIG32MQ02D/AIG32MQ03D
AIG32TQ02D/AIG32TQ03D
AIG32TQ12D/AIG32TQ13D
AIG32MQ04D/AIG32MQ05D
AIG32TQ04D/AIG32TQ05D
AIG32TQ14D/AIG32TQ15D
Communication standard Conforms to RS232C
(Non insulation type)
Note1)
Conforms to RS422
(Non insulation type)
Note1)
Communication
condition with
external
devices
Baud rate (bit/s) 9600, 19200, 38400, 57600, 115200 bps
Data length (bit) 7, 8
Parity
None, Odd, Even
Stop bit (bit)
1
Transmission distance
(Total length)
Max. 15 m
(Baud rate: 19200 bit/s)
Max. 500 m
(Baud rate: 115200 bit/s)
Protocol
- MEWTOCOL (Protocol for PANASONIC PLC: FP series)
- General-purpose serial (PANASONIC dedicated protocol)
- Other companies' PLC protocols (For the details, refer to the latest
GTWIN HELP.)
Connector
Connector terminal base (8-pin) Note2) 3)
Note1) It is internally isolated from the input power supply side (between +24V and 0V).
Note2) The (+) and (-) terminals are the power supply terminals for driving the main unit.
Note3) Regarding power supply voltage, please pay due consideration to the cable length so that the
applied voltage is within the operation voltage range.
Interface for transferring screen data
- USB port
Item
Specifications
Communication standard
USB1.1
Connector shape
Note1)
TYPE-B
Trasmission distance
Max. 5 m
No. of connected unit with PC 1 unit
Note1) Take care of handling of the connector not to add an excessive static electricy on the metal part
of the connector.
Note2) Screens can be transferred in one third less time via the Ethernet port.
(The speed varies depending on screen contents.)