6.7 GT21

6.7.1 General Specifications (GT21)

Item
Specifications
Rated voltage
24 V DC
Operating voltage range 21.6 to 26.4 V DC
Power consumption 4.8 W or less (200 mA or less)
Ambient temperature
0 to +50
°
C
Note1)
Ambient humidity
20 to 85% RH (at 25
°
C, non-condensing)
Storage temperature -20 to +60 °C
Storage humidity 10 to 85% RH (at 25 °C, non-condensing)
Breakdown voltage Between [power supply terminals] and [case]
500 V AC for 1 minute, Cutoff current 10mA (at default setting)
Insulation resistance
Between [power supply terminals] and [case]
100 M or more, 500 V DC, measured with megohmmeter (at default
setting)
Vibration resistance
10 to 55 Hz (1-minute cycle)
Amplitude: 0.75 mm,
10 min on 3 axes
Shock resistance 98 m/s
2
or more,
4 times on 3 axes
EC Directive applicable EMC Directive: EN61000-6-2, EN61000-6-4
Noise immunity 1000 V [P-P] or more, Pulse width 50 ns, 1µs between power supply
terminals (based on in-house measurements)
Note2)
Protective construction
IP65 (Initial value, evaluated by us)
Dustproof and drip-proof from front panel only (packing used on panel
contact surface) Note3)
Weight Approx. 230 g
Note1) When it is installed in a horizontal orientation (installed to make the liquid crystal face be topsid e)
or when the FP programmer II or C-NET adapter is connected to the TOOL port, the usable
range is 0 to +45 °C.
Note2) When using our exclusive cable.
Note3) When reattaching, replace waterproof packing.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net