Table 7.1a: Meter Conversion Natural Gas | Table 7.1b: Meter Conversion Natural Gas |
(U.S. Customary Units) | (SI Metric System) |
Burner inputs in Btu/hr for various meter timings and heating values. (Tables based on 2 cubic feet of gas through the meter).
Time that |
| Heat Value of Gas |
| ||
meter is |
| (Btu/cubic foot) |
| ||
read (sec) | 1000 | 1025 |
| 1050 | |
|
|
|
|
| |
25 | 288000 |
| 295200 |
| 302400 |
30 | 240000 |
| 246000 |
| 252000 |
35 | 205714 |
| 210857 |
| 216000 |
40 | 180000 |
| 184500 |
| 189000 |
45 | 160000 |
| 164000 |
| 168000 |
50 | 144000 |
| 147600 |
| 151200 |
55 | 130909 |
| 134182 |
| 137455 |
60 | 120000 |
| 123000 |
| 126000 |
65 | 110769 |
| 113538 |
| 116308 |
70 | 102857 |
| 105429 |
| 108000 |
75 | 96000 |
| 98400 |
| 100800 |
80 | 90000 |
| 92250 |
| 94500 |
85 | 84706 |
| 86824 |
| 88941 |
90 | 80000 |
| 82000 |
| 84000 |
95 | 75789 |
| 77684 |
| 79579 |
100 | 72000 |
| 73800 |
| 75600 |
105 | 68571 |
| 70286 |
| 72000 |
110 | 65455 |
| 67091 |
| 68727 |
115 | 62609 |
| 64174 |
| 65739 |
120 | 60000 |
| 61500 |
| 63000 |
125 | 57600 |
| 59040 |
| 60480 |
|
|
|
|
|
|
E.CHECK-OUT PROCEDURE
1.After starting the boiler, be certain all controls are working properly. Check to be sure that the limit will shut off the boiler in the event of excessive water temperature. This can be done by lowering the limit setting until the main burners shut down. When proper limit function is confirmed, return the dial to its previous setting.
2.To check operation of the ignition system safety
a.Turn gas supply off.
b.Set thermostat or controller above room temperature to call for heat. Watch for igniter glow at pilot burner.
Burner inputs in kW for various meter timings and heating values. (Tables based on 0.0566 cubic meters of gas through the meter).
Time that |
| Heat Value of Gas |
| ||
meter is |
| (MJ/cubic meter) |
| ||
read (sec) | 37.26 | 38.19 |
| 39.12 | |
|
|
|
|
| |
25 | 84.36 |
| 86.46 |
| 88.57 |
30 | 70.30 |
| 72.05 |
| 73.81 |
35 | 60.25 |
| 61.76 |
| 63.26 |
40 | 52.72 |
| 54.04 |
| 55.35 |
45 | 46.86 |
| 48.03 |
| 49.20 |
50 | 42.18 |
| 43.23 |
| 44.28 |
55 | 38.34 |
| 39.30 |
| 40.26 |
60 | 35.15 |
| 36.03 |
| 36.90 |
65 | 32.44 |
| 33.25 |
| 34.06 |
70 | 30.13 |
| 30.88 |
| 31.63 |
75 | 28.12 |
| 28.82 |
| 29.52 |
80 | 26.36 |
| 27.02 |
| 27.68 |
85 | 24.81 |
| 25.43 |
| 26.05 |
90 | 23.43 |
| 24.02 |
| 24.60 |
95 | 22.20 |
| 22.75 |
| 23.31 |
100 | 21.09 |
| 21.62 |
| 22.14 |
105 | 20.08 |
| 20.59 |
| 21.09 |
110 | 19.17 |
| 19.65 |
| 20.13 |
115 | 18.34 |
| 18.80 |
| 19.25 |
120 | 17.57 |
| 18.01 |
| 18.45 |
125 | 16.87 |
| 17.29 |
| 17.71 |
|
|
|
|
|
|
c.Igniter will continue to glow for 30 seconds, de- energize for 30 seconds, then
d.Turn gas supply on.
e.Reset the boiler and control by following Operating Instructions.
f.Observe boiler operation through one complete cycle.
26